20 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Continued from the previous page
Signal
Suggestions
Protection parameter configuration error: make sure that threshold I4 and time t4 are
compatible with the minimum values required for self-supply
Check:
• Rating plug of model compatible with Ekip Touch and CB size
Configuration
• If present, protection parameters do not conflict with size of current of unit details
on page 42)
• In the absence of Vaux threshold I4 and/or I41 > 100 A
• In the absence of Vaux time t4 and/or t41 > 100 ms
• RC protection active and Rating Plug not RC
Invalid Date
Wrong date and time: set in Settings-System-Date and Settings-System-Time
Ekip CI module not detected or absent, with Ekip M Touch and Open Mode
Ekip CI
configuration = Normal
Problem of Ekip Com Hub module with: certificates, connected devices, missing
Ekip Com Hub
Com modules (RTU or with Ethernet connection), API TLS device, Hub events, parsar
configuration
Fault in Ekip Link module: check for loss of connection with one or more actors
Ekip Link Bus
(modules) connected to Link Bus
Ekip Sign 3T
Alarm for connection of one or more analog inputs to Ekip Signalling 3T module
connection
Ekip Sign 3T
One or more thresholds of the Ekip Signalling 3T module has/have been exceeded
threshold
Internal error
Internal error; contact ABB if this typoe of error occurs
Fault with Ekip Com modules: synchronization problem of SNTP synchronization
SNTP error
reference module
Measuring Error
Measurement module parameter reading error, contact ABB
Ethernet
No external cable on one or more Ekip Com modules with Ethernet connection
disconnected
IEEE1588 synch
Synchronization problem of IEEE 1588 synchronization reference module
MAC Address
Ekip Com module detected with incorrect / not allowed MAC address, contact ABB.
Ekip Installation
Installation error between HMI and Mainboard, contact ABB
Measuring
Install Measurement module (Settings-Circuit breaker-Installation-Measuring-Install)
installation
menu
RatingPlug
Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and check
Installation
connection if there are further faults
Maintenance alarm: carry out maintenance and then reset the alarm via Ekip Connect
Maintenance
(see page !da duplicazione!112)
Rating plug
Rating plug not present, value or size incompatible with Ekip Touch parameters
Zone Selectivity
Error in zone selectivity connections (Hardware Selectivity)
Diag
S.G.R. Toroid
Check connection and state of toroid
Sensor L1/L2/
Fault in connection of sensors to Trip unit; check status of sensors, including external
L3/Ne
Neutral, or call ABB
Configuration
TFTP server enabled and/or configuration session open on module Ekip Com
Session
IEC61850 or Ekip Hub
The software versions between Mainboard and display (Ekip Touch) are not compatible
with each other: To restore compatibility, please consult ABB.
Software Not
NOTE: modification of all parameters is inhibited via display; if present,
Compatible
protections L, I and Iinst are active and function with the parameters prior to the
alarm (parameters of previous unit are active if display has been replaced)
CB status
CB state incorrect (esample: current present but CB in open state)
Switchboard Actor
Check configuration and connection of Ekip Link module
communication Error
Disconnection of Trip coil detected, check functionality
TC disconnected
Check Trip coil, status of the terminal and cables connecting to Ekip Touch
Contact Wear
Make sure that the contacts/poles are in good condition.
Continued on the next page
Management operations | 2 - Maintenance and troubleshooting