2 - Maintenance and troubleshooting

Introduction Correct maintenance of the unit and connected devices ensures they operate correctly over time.
Inspections and general
cleaning
Inspection of Ekip Touch Perform the inspections described in chapter 1 - Putting into service, including an inspection of the state or
Maintenance schedule The frequency with which Ekip Touch maintenance is scheduled differs, depending on the conditions in the
Alarms displayed and
suggestions
19 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
The maintenance operations must be performed by expert personnel, as required by the safety regulations
and maintenance schedule (see recipients, Safety requirements and Maintenance schedule).
If faults are discovered, find out what is causing them and eliminate them before putting the unit back into
service.
WARNING! Detecting faults must only be managed by (electrically) skilled persons
(IEV 195-04-01: person with relevant education and experience to enable him or
her to perceive risks and to avoid hazards which electricity can create), as it may be
necessary to perform insulation and dielectric tests on part or all the installation
Perform the following inspections:
• check to make sure that Ekip Touch is clean. Remove any dust and traces of other materials with a clean,
dry cloth (use a mild detergent if necessary; a laminate thinner such as Henkel 273471 or Chemma 18 or
equivalent can be used if there is a heavy coating of dirt)
• check that there are no foreign objects near the connectors or terminals
the wiring, modules and accessories:
• verification of alarms
• check that the modules (terminal box and external modules) are present and connected
• check zone selectivity connections
• check opening and closing actuators
NOTE: the limitations and notes given for each point in the respective paragraphs are applicable
installation site:
Standard environments
Frequency of
One year or 2000 operations or after
maintenance
tripping due to short circuit
By activating and using Predictive Maintenance in ABB Ability (EDCS) on the specific switch, you can suggest
a different maintenance frequency.
A list of faults that may appear on the Ekip Touch display is given below along with suggestions on how to
resolve them:
Signal
Suggestions
Numerical alarm
Internal error; contact ABB if this typoe of error occurs
(e.g. 30002)
Battery low
Change the battery (See 1SDH001000R0509 kit sheet)
Unit on with auxiliary supply, Local Bus parameter enabled but connection to modules
not present, incorrect or communication lost (for more than five seconds); check:
Local bus
• connection and powering of modules in terminal box or external
• that the moldules connected are compatible with Ekip Touch
CB undefined
Check the circuit-breaker status signal contacts
Trip fail command
CB has failed to open and/or current still present after a TRIP command: comply with
(BF)
the procedure proposed in the next chapter 'Faults, causes and remedies'
(l
).
ink
Management operations | 2 - Maintenance and troubleshooting
ABB | SACE Tmax XT
Dusty environments
(level of dust measured > 1mg/m3)
Every six months or 1000 operations or
after a short-circuit trip