Interface the module has three signaling leds:
Configurations Resistors can be connected to the CAN bus by configuring the dip-switches at the side of the module:
147 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Figure 44
LEDs
Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on and
Power
communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per second):
module on and communication with Trip unit absent.
Indicates the communication status on the bus:
Network
• off: device off line (with Status led off)
Status (1)
• on steady: device on line, and assigned to a master (operating condition)
• on flashing: device on line, but not assigned to a master (device ready to communicate)
Indicates the communication status on the bus:
Network
• Off: no error.
Status (2)
• On fixed: device in bus off, or Network Power absent.
• On flashing: I/O connection (cyclic data) in timeout
the device has not yet sent the Duplicate ID sequence in line
(1)
ON
1 2 3 4
Figure 45
Resistor
Dip
Description
120 Ω termination resistor
Rterm
1 and 2
Move dip-switches 1 and 2 to the ON position to connect Rterm
IMPORTANT:
• move the dip-switches before connecting the module to Ekip Supply and the network
• the termination resistors must never be included in the nodes; inclusion of this capacitance
could lead to a network with improper termination (impedance too high or too low), which could
potentially cause a failure. For example, removal of a node comprising a termination resistor
could lead to network failure
• the termination resistors must never be installed at the end of a drop line but only at the ends
of the main trunk line
2
1
, or in the error condition (with Status led on)
(1)
External electronic accessories | 4 - Ekip Com DeviceNet TM
ABB | SACE Tmax XT
Default
Off