ABB SACE Tmax XT7 Operation And Maintenance Manual page 169

For ekip touch trip units, tmax low voltage moulded-case circuit-breakers xt7
Hide thumbs Also See for SACE Tmax XT7:
Table of Contents

Advertisement

Interface the module has three signaling leds:
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
167 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Figure 51
LEDs
Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
Power
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Indicates the communication state:
Link (1)
• off: incorrect connection, signal absent.
• on steady: connection correct
Indicates the communication state:
Activity (2)
• off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
available in the Settings menu (page 37).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter
Description
Enable
Switches communication between module and server on/off.
Defines whether the module has the dynamic (Off) or static (On)
Static IP address ON
IP address.
If = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected
Static Network Mask
Enables the subnet mask to be selected
When there are several subnets, enables the IP address of the
Static Gateway address
node to which the module is connected to be selected
Allows the SNTP protocol for distribution of the clock and
Enable SNTP client
synchronization signal to be enabled.
SNTP Server Addr.
Allows the network server that supplies the SNTP to be set.
Password
code required to register module on Cloud
Enables the firmware of the module to be updated. There are two
parameters:
Remote firmware update
• Enable, to configure firmware download
• Automatic, to automate module updating
2
ABB | SACE Tmax XT
1
Default
Off
0.0.0.0
0.0.0.0
0.0.0.0
Off
0.0.0.0
---
Off
Automatic
External electronic accessories | 10 - Ekip Com Hub