4 - Datalogger

Presentation
Datalogger
Function When the datalogger is enabled and activated (RESTART), Ekip Touch continuously acquires data by filling
Parameters 1 The parameters and commands of the function are available in the Settings menu (page 37).
117 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
The datalogger is a function which allows data associated with a trigger event to be recorded. The following
data are recorded:
• Analog measurements: line-to-line voltages and phase currents
• Digital events: protection events or alarms, circuit-breaker status signals, protection trips.
One or two independent recordings can be configured and, via Ekip Connect, all the associated information
can be downloaded, displayed and saved.
and emptying an internal buffer (B).
If a trigger event (A) occurs, Ekip Touch interrupts acquisition (STOP) immediately or after a time that can
be set by the user (C) and stores all the data of the window (D), which can then be downloaded to a PC for
reading and analysis.
IMPORTANT: the function requires an auxiliary voltage supply
Figure 35
Parameter
Description
Activates/deactivates the function and its availability in the parameters
menu
Enable
NOTE: il the enable command is hidden when at least one
datalogger is activated
Determines the number of recordings (1 or 2)
Num. of
NOTE: the recordings share the settings of the sampling
Datalogger
frequency and type of memory
Establishes the number of samples acquired per second and the
recording window.
Four options are available: 1200 Hz (window= 13.6 s), 2400 Hz (6.8
s), 4800 Hz (3.4 s), 9600 Hz (1.7 s)
Sampling
NOTE:
frequency
• A high frequency allows the data to be analyzed more
accurately
• if there are two dataloggers, the recording window of each
recording is halved
Datalogger 1
Menu with the parameters of each Datalogger: trigger event, recording
and 2
delay and Restart/Stop commands
Restart and
Synchronized start and stop commands of the two dataloggers, valid
Stop Both
and available with Num. of Datalogger = 2
ABB | SACE Tmax XT
Default
Off
1
9600 Hz
Ekip Touch - Measurements | 4 - Datalogger