ABB SACE Tmax XT7 Operation And Maintenance Manual page 159

For ekip touch trip units, tmax low voltage moulded-case circuit-breakers xt7
Hide thumbs Also See for SACE Tmax XT7:
Table of Contents

Advertisement

Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
157 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
correctly:
Information
Description
Identifier and SW version of the module
SN and version
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
IP address
set via the menu in the event of a static IP.
NOTE: without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the modules
Network Mask
belong and enables modules to be searched for within a defined set of recipients.
IP address of the node to which the module is connected, in the presence of several
Gateway address
subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
communication:
Parameter
Description
Enable IEEE
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
1558
IEEE 1558
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
Master
IEEE 1558 Delay
Allows the data exchange mode between module and master, either
mechanism
Peer-to-Peer or End-to-End, to be selected.
Enable client
Allows the SNTP protocol for distribution of the clock and
SNTP
synchronization signal to be enabled
ANTP Server
Allows the network server that supplies the SNTP to be set.
address
Time zone
Defines the time zone to be used for synchronism
Daylight Saving
Used to select whether daylight saving time is present (ON) or not
Time
(OFF) in the country to which the synchronization time refers
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
communication:
Information
HW and Boot version
Flash CRC status and result
Ekip Link status
SNTP Server Error
SNTP Server Synchronization
IEEE 1558 status
.
(1)
(1)
Description
General module information
Information about the correctness of the SW in the module
Signals Ethernet cable connection errors
Error in communication with SNTP server
State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
Master Active) or absence (PTP Master but Passive) of a higher level
master
External electronic accessories | 7 - Ekip Com EtherNet/IP TM
ABB | SACE Tmax XT
Default
OFF
OFF
End-to-End
OFF
0.0.0.0
+00:00
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents