For ekip touch trip units, tmax low voltage moulded-case circuit-breakers xt7
Hide thumbs Also See for SACE Tmax XT7:
Table of Contents

Advertisement

OQ Protection
t
Q27
OP Protection
t
P26
66 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Function
The protection sends a TRIP command if one or more of the reactive power values detected by the unit
exceed threshold Q27 for longer than t27.
OQ
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 88)
• the graph with trip curve (page 104)
t27
Parameters
Q
Parameter
Enable
Trip Enable
Threshold Q27
Time t27
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 78).
Function
The protection sends a TRIP command if one or more of the active power values detected by the unit exceed
threshold P26 for longer than t26.
OP
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 88)
• the graph with trip curve (page 104)
t26
Parameters
P
Parameter
Enable
Trip Enable
Threshold P26
Time t26
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 78).
Description
Activates/deactivates the protection and its availability in the
parameters menu
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
Establishes the value that activates the protection.
The value is given as both absolute value (kVAR) and relative value
(Sn) and can be set within the range: 0.4 Sn to 2 Sn in 0.001 Sn steps
This is the trip time of the protection; the value is given in seconds and
can be set within a range: 0.5 s to 100 s, in 0.5 s steps
Description
Activates/deactivates the protection and its availability in the
parameters menu
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
Establishes the value that activates the protection.
The value is given as both absolute value (kW) and relative value (Sn)
and can be set within the range: 0.4 Sn to 2 Sn in 0.001 Sn steps
This is the trip time of the protection; the value is given in seconds and
can be set within a range: 0.5 s to 100 s, in 0.5 s steps
ABB | SACE Tmax XT
Default
OFF
OFF
1 Sn
1 s
Default
OFF
OFF
1 Un
1 s
Protections | 11 - Power protections