Figure 3-1. Ups Cabinet Dimensions - Three Upm (Front View) - Eaton Power Xpert 825/550 Installation And Operation Manual

450–825 kva
Table of Contents

Advertisement

UPS INSTALLATION PLAN AND UNPACKING
Model
Rating
Power Xpert
650 kVA (IOM)
9395-825/650
Power Xpert
750 kVA (IOM)
9395-825/750
Power Xpert
825 kVA (IOM)
9395-825/825
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
t
3-4
Power Xpert
9395 UPS (450–825 kVA) Installation and Operation Manual
Input/Output
Heat Rejection
BTU/hr  1000 (kg-cal/hr)
Voltage
400/400
480/480
400/400
480/480
400/400
480/480
Figure 3‐1. UPS Cabinet Dimensions – Three UPM (Front View)
Ventilation Required for Cooling Air Exhaust
125 (31613)
127 (31933)
Approximately 2478 liter/sec (5250 CFM)
145 (36476)
146 (36845)
Approximately 3304 liter/sec (7000 CFM)
159 (40124)
161 (40530)
S
www.eaton.com/powerquality
164201725 Rev 9
With Field Installed UPM:
Dimensions are in millimeters [inches].