Mounting and wiring
3.6.5

ELX1052 - Contact assignment

Fig. 21: ELX1052 - Contact assignment
Terminal point
Designation
No.
Input 1
1
2
3
Uv1
4
Input 2
5
6
7
Uv2
8
LED Display
The following table is assigned to the respective LED number of a channel.
Input LED
Error LED
off
on
off
off
on
on
on
off
28
Description
Input Channel 1
not implemented
not implemented
Sensor supply Channel 1
Input Channel 2
not implemented
not implemented
Sensor supply Channel 2
Meaning
Error detection: open- circuit on channel (I < 200 µA typ.)
Usual operation: NAMUR sensor on channel in non-conductive state
("0"; according to IEC 60947-5-6)
Error detection: short-circuit on channel (I > 6.3 mA typ.)
Usual operation: NAMUR sensor on channel in conducting state
("1"; according to IEC 60947-5-6)