Page 1
178 142 52-3 P93783 2023-03-17 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B 30 A2.2 RME LMO24.255C2E DV 57 C Translation of the original instructions.
Page 2
1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\download 2. www.bentone.com\ nedladdning eller scanna or scan QR-code. download eller scan QR-koden.
Make sure that the burner is suitable for the application (see Technical • Data). All components must be installed without being bent, twisted or • subjected to mechanical or thermal forces that affect components. 165 105 01-2 2021-12-07 Bentone...
Page 5
When in operation, the burner’s noise level can exceed 85 dBA – use • hearing protection! - Operation: Carry out all stipulated settings, service and inspection work within • the set time. • If the oil burner control has a solid red light, contact your installer. Bentone...
Annual cleaning and checking for the presence of water in the tank • should be done to avoid corrosion and microorganisms. 165 405 06 2021-12-07 Bentone...
Fuel oil according to DIN 51603-1. • Fuel oil A Bio 10 according to DIN 51603-6. • Dimensions B 30 A2.2 øB øC ØB ØC 174/315 * Min. recommended distance to floor. Dimensions flange 2.1.1 ø108 165 305 22-4 Bentone...
6.0-17.0 kg/h 72-200 kW mbar Do not exceed working field. -0,5 Basic settings - Fuel oil Air settings Nozzle assembly Scale <˚ Burner output Scale nozzle assembly and air damper without damper motor. Settings air damper with damper motor. Bentone...
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air intake to the air duct that opens into an appropriate location. Installation must be done so it does not prevent air supply to the burner. Bentone...
4,00 11,88 141 12,70 150 13,47 160 14,20 168 14,89 176 15,56 184 16,19 192 16,80 199 17,39 206 The table applies to oil with a viscosity of 4.4 mm /s at a density of 830 kg/m RME energy content 10,4 kWh/kg Bentone...
The cables of the safety system must be separated so that the outgoing signal is not placed in the same cable as the incoming signal. Wiring diagram E106356 Brown Blue Green Yellow Gn/Ye Green/Yellow Black Grey White Orange Violet 165 205 56-2 Bentone...
< 1 s < 1 s Ambient temperature -5 - +60°C -20 - +60°C Min detector current required (with fl ame) 45 µA dc 45 µA dc Max perm. detector current (without fl ame) 5.5 µA dc 5.5 µA dc Bentone...
If the reset button is instead kept pressed a second time for at least 3 seconds, you can, via an interface, obtain the corresponding information on a computer or flue gas analyser. To return to normal operation: Press the reset button for 1 second. Bentone...
Bleed the oil system. The oil pump/oil preheater may be damaged if • run dry. The vacuum in the suction line should not fall below 0.3 bar during start-up. 165 205 19-3 Bentone...
Electrical connection must be done in accordance with the applicable • regulations. Burners must be connected to an all-pole switch. • • Connection must conform to the wiring diagram. Use appropriately sized fuses. • If any electrical connection is used other than that recommended by Enertech, there may be a risk of damage to property and personal injury. Bentone...
Connect the burner electrically, (see chapter Service). Check oil line seals When the burner has been installed and put into operation, the tightness of the various coupling elements should be checked, in case of leakage - retighten the coupling elements. 165 105 04-2 Bentone...
Stage 1 Fuel, Stage 2 Solenoid valve 2 Stage 2 Insert Stage 2 Selection of output and connection between the different power stages must be selected and adjusted so that the system achieves good functionality. 165 405 24-2 Bentone...
Models gear sizes ”45” and ”55” have a piston with a bleed slot to avoid build up of pressure in the nozzle and suction lines during shut down due to the expansion of oil caused by nozzle line heaters. Bentone...
(D-H) max. = 4,5 m 150 150 139 150 108 150 150 150 150 **Q = pump capacity @ 0 bar / Pumpenleistung bei 0 bar Two pipe lift system capacité de l'engrenage à 0 bar/portata della pompa a 0 bar. Bentone...
Page 24
5 min. (a condition is that the pump is being lubricated during operation). The tables state the total suction line length in metres at a nozzle capacity of 9,5 Gph. Max. permissible pressure at the suction and pressure side is 2,0 bar. Bentone...
Loosen the pump cover’s screws. Remove the fi lter and gasket Mount new gasket and fi lter Refi t the cover Open the oil supply Start the burner and check seals and combustion When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test must be carried out following installation. Bentone...
Ignition system with fl ame guard 10 years 250,000 cycles UV fl ame sensor 10,000 h 500,000 cycles Damper motor 10 years 500,000 cycles Contactor The burner and its components must be recycled according to applicable regulations. 165 405 08-2 2022-10-09 Bentone...
Do not clean. Refi t fan housing and fi xing fl ange, lock with nut (G). Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test must be carried out following installation. 165 405 13 Bentone...
Refi t the intake grille. damper motor. Release the button on the damper motor. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test must be carried out following installation. 165 405 16 Bentone...
Release the button on the damper motor. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test must be carried out following installation. 165 405 18 Bentone...
Replace drive shaft coupling on pump. Refi t coupling, pump and motor, making sure drive shaft is connected correctly at both ends. Switch on the main power and open the fuel supply. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test must be carried out following installation. 165 405 32 Bentone...
Switch on the main power and open the fuel supply. Bleed the pump, start the burner and set the correct oil pressure (see Technical data for correct output). Start burner and check/adjust combustion. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test must be carried out following installation. 165 405 21 Bentone...
Note the connection of the existing component and disassemble. Fit new component with same connection or with specified alternative connection. Switch on the main power and check the operation of the new component. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 105 11-3 Bentone...
• Check tightness of fasteners. Check fan wheel for damage and contamination (replace if necessary). • Check motor shaft and bearings. If they are worn, replace the motor. • Use screw to attach the vibration sensor. 165 405 22 Bentone...
Preheater temperature too low Check preheater function New oil type Adjust the preheater‘s set operating temperature Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. 165 105 09-2 2021-01-21 Bentone...
Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. Temperature of the oil from the tank is too low, increase the temperature of oil from tank Clean the pump filter Bentone...
Change the oil or the pump‘s oil parameters Pump worn Replace the pump Pump run using impure oil that has worn the Replace pump and install self-cleaning pump out prematurely filter in the oil system Blocked pump filter Check, clean pump filter Bentone...
Log of flue gas analysis Tel. no: Owner Adresss Tel. no: Installation Boiler Type Make Power kW Burner Type Model Serial no. Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke number Flue gas temp. °C Setting brake disc Setting Air damper Pump pressure...
Page 39
EU Declaration of conformity Bentone Oil Burners Type: BF 1 ST 133 B 40 B 65 ST 108 ST 146 B 45 B 70 ST 120 B 30 B 55 B 80 This declaration of conformity is issued under the sole responsibility of the manufacturer.
Page 40
UK Declaration of conformity Bentone Oil Burners Type: BF 1 ST 133 B 40 B 65 ST 108 ST 146 B 45 B 70 ST 120 B 30 B 55 B 80 This declaration of conformity is issued under the sole responsibility of the manufacturer.