Basic settings - HVO/XTL

2.5
1
Scale
10
8
6
4
2
0
55
85,2
Scale nozzle assembly and air damper without damper motor.
1
Settings air damper with damper motor.
2
Flame signal
When operating at high power or low air excess and HVO/XTL is used as fuel,
the flame signal may deteriorate (blue flame), the signal lamp in the reset
button flashes green.
By lowering the air velocity or changing the flame detector to QRC1 A1, the
flame signal can be improved.

Technical specification

2.6
Main supply
1)
Max fuse rating
El
preheater excluded
min
El
preheater excluded
max
P
SB
NO
-class
X
(GCV) preheater excluded 119mg/kWh
NO
X
Noise level
Max operating current, see data plate.
1)
Measurements according to EN 15036-1:2006
Alt.1 The noise level of the burner can be reduced by equipping the burner
with silencer. Installation must be done so it does not prevent air supply
to the burner.
Alt.2 The burner's noise level can be reduced by connecting the burner's air
intake to the air duct that opens into an appropriate location. Installation
must be done so it does not prevent air supply to the burner.
Air settings
Nozzle assembly
115
144
B 30 A2.2
230V, 1~, 2.6/2.8A, 50Hz, IP20
6.3A
1.40A, 297W
1.50A, 315W
0
4
82dBA
2
Air
100
80
60
40
20
0
kW
175
Burner output
9