Bentone STERLING 40 ST108PL Installation And Maintenance  Instruction

Bentone STERLING 40 ST108PL Installation And Maintenance Instruction

Advertisement

178 016 13
Providing sustainable energy solutions worldwide
Installation- and maintenance instruction
STERLING 40 ST108PL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the STERLING 40 ST108PL and is the answer not in the manual?

Questions and answers

Summary of Contents for Bentone STERLING 40 ST108PL

  • Page 1 178 016 13 Providing sustainable energy solutions worldwide Installation- and maintenance instruction STERLING 40 ST108PL...
  • Page 3 DESCRIPTION Components 1. Reset button 8. Blast tube 15. Indication, air damper 2. Control box 9. Ignition electrodes 16. Fan wheel 3. Ignition transformer 10. Connecting pipe 17. Adjustment, air damper 4. Ignition cables 11. Air damper 18. Photoresistor 5. Nozzle assembly 12.
  • Page 4: Technical Data

    TECHNICAL DATA ST 108 PL 6-7-21,5-10 Dimensions Incl. lange A Incl. lange B Incl. lange C Incl. lange D Burner tube Length of burner tube Measure B Measure B Measure B Measure B Output range and nozzles recommended Burner tube Oil capacity Outputy Recommended...
  • Page 5 TECHNICAL DATA Dimensions Flange A Flange C ø90 ø89,7 130-150 Flange B Flange D ø89,5 ø90 136-150 125-150 171 215 76 07-01...
  • Page 6: General Instructions

    GENERAL INSTRUCTIONS General rules Measures to raise the temperature: Adjustment of burner Insulate the chimney in cold attics The installation of an oil burner To obtain a correct adjustment a lue gas analysis and a temperature Install a chimney liner should be carried out in accordance Install a draught regulator (dilutes the with local regulations.
  • Page 7 MAINTENANCE OF OIL BURNER Warning: Before doing any service switch off power at the main switch and cut off the oil supply Service of burner head and nozzle assembly 171 305 68 07-01...
  • Page 8 ELECTRIC EQUIPMENT Oil burner control: LOA21... / LOA24.../ LMO14.../ LMO24... List of components Wiring diagram A1 Oil burner control A2 Twin thermostat F1 Fuse, max. 10A H1 Alarm lamp H2 Signal lamp (optional) M1 Burner motor P1 Time meter (optional) R1 Photoresistor S3 Main switch T1 Ignition transformer...
  • Page 9 ELECTRIC EQUIPMENT Function 3-4. Operating position Switch on operating switch and twin thermostat If the burner operation is interrupted by means of The burner motor starts, an ignition spark is formed, the main switch or the thermostat, a new start takes the prepurge goes on till the prepurge period ex- place when the conditions in accordance with point 1 are fulilled.
  • Page 10 INSTRUCTIONS PUMP TYPE DANFOSS BFP11 Technical data Viscosity range: 1,3-12,0 mm Pressure range: 7-15 bar Oil temperature: -10 to +70°C Components 1. Nozzle port G 1/8" 2. Pressure gauge port 3. Pressure adjustment, 4mm allen key 5. Vacuum gauge port G 1/8" 6.
  • Page 11 INSTRUCTIONS PUMP TYPE DANFOSS BFP11 Function danfoss BFP11 When the oil pump is started, oil is drawn from the suction connection (S) through the ilter (H) to the suction side of the gear wheel (C). The gear wheel then pumps oil to the pressure side and the oil is put under pressure.
  • Page 12 NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 0,40 1,33 1,41 1,49 1,56 0,50 1,66 1,76 1,86 1,95 0,60 2,00 2,12 2,23 2,34 0,65 2,16 2,29 2,42 2,54 0,75 2,49 2,65 2,79 2,93 0,85 2,83 3,00 3,16 3,32...
  • Page 13 NOZZLE TABLE Pump pressure bar kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h kg/h Mcal/h 0,40 1,63 1,70 1,76 1,82 0,50 2,04 2,12 2,20 2,28 0,60 2,45 2,55 2,64 2,73 0,65 2,65 2,75 2,86 2,96 0,75 3,08 3,18 3,30 3,42 0,85 3,47 3,61 3,74 3,87...
  • Page 14 FAULT LOCATION Burner fails to start Situation Possible causes Remedies Motor runs Flame instability Burner pre-purges Check nozzle to burner head dimension Incorrect head settings and electrode position Low oil pressure Check oil pressure Flame occurs Excess air Adjust air damper Burner locks out Check that photocell is clean and unobstructed...
  • Page 15 In that the burner conforms to the above mentioned standards it is awarded the CE mark. Indem der Brenner die obengenannten Normen und Richtlinien erfüllt, erhält der Brenner die CE-Kennzeichnung. Du fait de leur conformité aux directives mentionnées ci-dessus, les brûleurs Bentone bénéficient du marquage CE. Ljungby, Sweden, 150227 (27/02/15) Enertech AB, Bentone Division/ är kvalitetscertifierat enligt/...
  • Page 17 OIL BURNERS MAINTENANCE INSTRUCTIONS General information If the burner starts but does not ignite Keep the boiler room clean. Ensure that the boiler Make an attempt to start the burner. room has permanent fresh air intake. Switch off before Never make close repeated start attempts. dismantling the oil burner.
  • Page 20 Enertech AB. P.O Box 309, SE-341 26 Ljungby. www.bentone.se, www.bentone.com...

Table of Contents

Save PDF