Enter the desired value in the Current value column. The input value is converted to the data format
²
according to IEC 61850. Because of the associated quantization, the resulting display value can differ
from the input. In addition, the input value is rounded to 6 digits. The display is limited to 6 digits. There-
fore please note that, in case of small pulse weighting, minor changes to large metered values can not be
reflected in the display.
To transfer the value to the device, click the Set button.
²

Resetting Min./Max./Average Values

8.6.5
Resetting minimum/maximum/average values on the device:
To reset, open the Measured values menu on the device.
²
Switch to the corresponding function group and to the Minimum/maximum/average values.
²
You can reset the minimum/maximum/average values using the context-sensitive right Reset key.
²
Resetting minimum/maximum/average values with DIGSI 5:
Start the online mode with DIGSI 5.
²
Click (in the project tree bottom left) the Measured values menu item.
²
Double-click the selected function group and the measured-value window appears in the operating
²
range.
If you open the Min/Max/Average values tab in the measured-value window, you are shown the current
²
minimum/maximum/average values.
If you click the Reset button, you can reset the current values to 0.
²

Setting and Resetting Statistical Values

8.6.6
Setting and resetting statistical values on the device:
To set and reset, open the Measured Values menu on the device.
²
Switch to the Circuit Breaker function group.
²
You can reset the values if you select Statistical Values on the display via the context-sensitive Reset
²
key.
If you select one level lower, you are brought to the statistical values. The measured values are displayed
²
in primary values.
You can set the statistical values to the desired value via the right context-sensitive Change key. The
²
input value is converted to the data format according to IEC 61850. In addition, the input value is
rounded to 6 digits. The display is limited to 6 digits. Therefore please note that, in case of small pulse
weighting, minor changes to large metered values can not be reflected in the display.
Set the new value and activate acceptance with Enter.
²
Setting and resetting statistical values with DIGSI 5:
Start the online mode with DIGSI 5.
²
Click (in the project tree bottom left) the Measured values menu item.
²
Double-click the Circuit breaker function group and the measured-value window appears in the oper-
²
ating range.
If you open the Statistics tab in the measured-values window, you are shown the current statistical
²
values (see
You can reset the current values to 0 by clicking the Reset button.
²
Alternatively, you can set a value:
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-J, Edition 07.2022
Figure
8-40).
Operation in the Operating State
8.6 Edit Measured and Metered Values
199