Download Print this page

DAYLIFF PVm015 Installation & Operating Manual page 37

Pumpverter vfd controller

Advertisement

Fault
Fault
Code
Type
Over current
When
E007
Acceleration
(OVI)
Over current
during
E008
Deceleration
(OV2)
Over
voltage
When
running at
E009
Constant
Speed
(OV3)
DC Bus
Under
E010
Voltage
(UV)
Motor
Overload
E011
(OL1)
Controller
Overload
E012
(OL2)
Input Phase
E013
Failure
(SP1)
Output
Phase
E014
Failure
(SP0)
Reason
1. High input voltage
2. Regenerative energy
from the motor is too large
1. Dec time is too short
2. Load is too big
3. High input voltage
1. High input voltage
2. Load is too big
1. Low input voltage
1. Low input voltage
2. Wrong setting of motor
parameter
3. Motor locked rotor or
sudden big change of load
to small load
4. The power of motor is
too small
1. Acc time is too short
2. Restart the motor when it
is decelerating
3. Low input voltage
4. Load is too big
1. Loss of phase occurred
in power supply
1. Loss of phase occurred
in output side of main
6 35
Solution
Check the power supply
Avoid restarting the motor until it stops
completely
Increase Dec. time
Reduce load or use higher power
controller
Check the power supply
Install input reactor
Increase braking
Check the power supply
Check the power supply
Set the rated current of motor properly
Check the load, adjust the value of
torque boost
Select proper power motor
Prolong Acc time
Avoid restarting the motor until it stops
completely
Check the power supply
Select bigger capacity controller
Check the wiring, installation and the
power supply
Check the output wiring, cable and
motor

Advertisement

loading

This manual is also suitable for:

Pvm022Pvm075Pvm150