Code
Name
Low level
restart
0-300min 1min
b05.01
delay
Terminal
S1 & S2
b05.02
control
Accelerat
b05.03
ion time
Decceler
ation
b05.04
time
Maximu
m output
b05.05
frequenc
y
Frequenc
y upper
b05.06
limit
Frequenc
y
b05.07Hz
lower
b05.07
limit
Setting
Factory
Recommend
Range
Setting
0-3
2
Depe-
nds
0.1-
on
3600s
model
Depe-
nds
0.1-
on
3600s
model
10-600
50Hz
Hz
b05.07-
50Hz
b05.05
10Hz-
20Hz
Description
-ed Setting
Delay time in minutes for restart after
1min
water level switch recover
0: Invalid
1: Electric contact control
S1&COM-ON: Frequency rise
S2&COM-ON: Frequency drop
2:Manual/Auto control
S2&COM-OFF: Auto control
2
S2&COM-ON: Manual control
3:Terminal run/stop
S1&COM-ON: Run
S1&COM-OFF: Stop
S2&COM-ON: Manual control
S2&COM-OFF: Auto control
Ramp up frequency
10s
Ramp up frequency
10s
Maximum frequency
50Hz
Maximum running frequency
50Hz
Minimum running frequency
30Hz