DAYLIFF PVm015 Installation & Operating Manual page 25

Pumpverter vfd controller

Advertisement

Code
Name
Commun
ication
b03.00
Address
Slave
b03.08
Quantity
Fault
b03.09
Shift/
Standby
master
Sleeping
b04.00
function
Sleeping
b04.01
time
Wake up
pressure
0-20 bar 0.5bar
b04.03
bias
Sleeping
b04.04
Bias
Water
level
b05.00
control
Setting
Factory
Recommend
Range
Setting
-ed Setting
0-31
2
0-5
0
0-2
2
0-1
1
0-300s
5s
0-1bar
0bar
0-2
2
Description
00: Master Controller
01-05: Auxiliary controller (slaves)
06-31: Reserved
00-0N
Auxiliaries should be set as 01-on
0N on order assuming N auxiliary
controllers
0: None
Slave number, assume 1 master N
N
slaves, set as N
Fault Master Shift.
I f
i n v a l i d ,
If valid, Set Master as 0 and Slave 1
as 1; slave 1 to act as standby
0-1
master
W i t h Fa u l t s h i f t , c o n n e c t a
redundant transducer to the slave 1.
No need to modify other slaves.
0: Invalid
Automatically Stop when there is no
1
water consumption
Delay time in seconds
10s
Determines how low the pressure
falls before pump restarts during
sleep mode e.g. if setting (L)=3.0
0.5bar
bar, bias b04.03=0.5bar, the pump
will restart again when pressure falls
to 3.0-0.5=2.5bar.
The pressure fluctuation that allows
sleeping. If pressure rises by this set
0.5bar
value b04.04 for time b04.01, it
enters sleep mode.
Water level switch connection style;
1
0: Invalid 1: NC 2: NO
23
S e t
2 .
1: Valid