Relevant Parameter Setting
This example uses the pressure switch for control instead of the transducer (Wiring refer
to figure 1). Adjustment of the pressure switch cut-in and cut-out pressures should be
done before running. For example for 3bar water supply, then up contact adjust above
3bar (such as at 3bar), bottom electric contact below 3bar (such as at 2.8bar).
Factory
Code
Recommended
Setting
b00.00
65535
b02.08
1.0%
b08.01
~
b08.05
b00.02
0
20
b01.02
b05.02
2
0
b01.16
b05.00
2
001
b05.01
b05.03
b05.04
Password of entering parameter groups. Factory set is
65535
65535, it can be modified by b06.09
All feedback lost detecting value, this application need
0.0%
not pressure detect, set the parameter 0
Ensure normal operation must input parameter
according to nameplate of motor
Motor rotating direction, set according to the actual
x
motor wiring of spot. Make sure the motor is running in
forward direction
Low pressure running time should be increased for
use-cases where water pressure rises slowly. The LP
running time b01.02 determines the maximum time
xx
that pressure is below cut-in pressure. Controller stops
and alarms when the pressure below cut-in pressure
lasts for a duration three times of the setting b01.02.
Terminal S1S2 control set for pressure switch control
1
Restart after power on considering unattended
x
management, set parameter to 1
Water level (terminal S3) switch type according to the
x
switch type in use
1. NC Valid
S3 action delay time, In case slow incoming water
xxx
leads to short run time durations
Acc. and Dec. time. It is recommended to set equal or
above 20s, a short acc./dec. time leads to rapid pump
cycling
Description
6 30
2: NO Valid