DAYLIFF PVm015 Installation & Operating Manual page 12

Pumpverter vfd controller

Advertisement

Function
Name
Code
All Lower
b01.06
Limit
Corresponding
Setting of AI1
b01.07
Lower Limit
Al1 Higher
b01.08
Corresponding
Setting of Al1
b01.09
Higher Limit
Al1 Filtering
b01.10
Time
AI2 Lower
b01.11
Limit
Corresponding
Setting of AI2
b01.12
Lower Limit
AI2 Lower
b01.13
Limit
Corresponding
Setting of AI2
b01.14
Higher Limit
AI2 Filtering
b01.15
Time
Restart After
b01.16
Power-on
Control Mode
b01.17
PID Source
b02.00
Selection
PID Feedback
Source
b02.01
Selection
Factory
Setting Range
Setting
0.00~
1.00V •
10.00V
-100~100% 0.0%
0.0~10.0V 5.00V
-100~100% 100%
0.00-10.00s 0.10s
0.00-10.00V
1.00V
-100~100% 0.0%
0.00-10.00V 5.00V
-100~100% 100%
0.00~10.00s 0.10s
0~1
0~1
0~1
0~1
10
Lower limit use to transducer zero
setting
Higher limit use to accordant
display and transducer pressure
When display smaller than
gauge increase higher limit.
When display is greater than
gauge, decrease higher limit.
When analog input is interfered,
prolong filtering time so as to
increase the ability of anti-
interference but decreases the
sensitivity.
Corresponding relationship of
transducer parameter setting:
Corresponding
Pressure Setting
0
Lower
Limit
Figure 5.1.1 Transducer
Parameters
0
0:Invalid
0:Synchronous
1
0
0:Keypad
0
0:A11
1:Reserved
Description
Max Range of
Transducer
Upper
Limit
1:Valid
1:Master-Slave
1:Reserved