Fault
Fault
Code
Type
High Water
Pressure
HL
and Low
Water Level
(HP+LL)
Sensor
E022
Fault
IGBT Ph-U
E001
Fault
(OUTI)
IGBT Ph-V
Fault
E002
(OUT2)
IGBT Ph-W
E003
Fault
(OUT3)
Over
current
E004
When
Acceleratio
n (OC1)
Over
current
E005
during
Deceleratio
n (OC2)
Over
current
When
E006
running at
Constant
speed
(OC3)
Reason
1. Abnormal sensor
2. The parameter B01.00
setting value is too small
3. Water level is too low
4. Abnormal water level
switch
5. Wrong setting of water
level switch style parameter
1. Pressure transmitter
disconnected
2 . W r o n g p r e s s u r e
transmitter wiring
3. Pressure transmitter
short circuit
4. Pressure transmitter
breakdown
1. Acc/Dec time is too short
2. IGBT module fault
3. Malfunction caused by
interference
4. Grounding not properly
done
1. Acc time is too short
2. Low input voltage
3. Low power of controller
1. Dec time is too short
2. Load is too big
3. Controller undersized
1. Sudden change of load
2. Low input voltage
3. The power of controller
is small
6 34
Solution
Check the installation of pressure
transmitter
Check the parameter b01.00 (setting
value is too small)
Check the water system
Check the condition of the control
terminal S3
Check the parameter
correct
Check the cable between pressure
transmitter and controller
Check the sensor whether normal
Increase Acc/Dec time
Check external equipment and
eliminate interference
Check earth wiring
Contact Dayliff retailer
Prolong Acc time
Check the power supply
Select bigger power controller
Prolong Dec time
Increase braking time
Select bigger power controller
Check the load
Check the power supply
Select bigger capacity controller
B05.00 and