6.4 Parameter Settings for Single and Multi-Pump constrant
Pressure Control
Single pump constant pressure control
Ÿ Set all parameters in table below on controller except b03.00-b03.09, b05.10
Multi-pump constant pressure control: One master Pump, all other
pumps slaves
Ÿ Master controller should have pressure transducer connected
Ÿ Set all parameters in table below for master pump controller
Ÿ Set following parameters for slave pump controllers: b00.00, b00.02, b02.08=0,
b03.00, b03.08, b03.09, b08.01-b08.05
Multi-pump constant pressure control: One master, all other pumps
slaves with one slave set as standby master
Ÿ Both master and standby master controllers should have pressure transmitters
connected.
Ÿ Set all parameters in table below for master pump controller
Ÿ Set all parameters in table below for slave pump controller that used as standby
master
Ÿ Set following parameters for slave pump controllers: b00.00, b00.02, b02.08=0,
b03.00, b03.08, b03.09, b08.01-b08.05
Code
Code
Name
Name
Debuggi
ng
b00.00
Password
Pressure
setting
b00.01
value
Motor
b00.02
rotation
High
water
pressure/
b01.00
Level
alarm
value
Setting
Setting
Factory
Factory
Recommend
Recommend
Range
Range
Setting
Setting
0-65535
65535
0-
100 bar 3 bar
0-1
0
0-100
8 bar
bar
Description
Description
-ed Setting
-ed Setting
Retain as per the Factory default.
65535
Can be modified by b06.09
S e t a c c o r d i n g t o t h e a c t u a l
4 bar
requirements of the user e.g. 4 bar
0- Forward 1- Reverse
Ensure pump motor is running in
0
correct direction
When the pressure is higher than this
preset value, the controller halts,
8 bar
alarms and displays HP .