DAYLIFF PVm015 Installation & Operating Manual page 24

Pumpverter vfd controller

Advertisement

Code
Name
Maximu
m
Transduc
b01.05
er
setting
range
AI1 lower
b01.06
limit
AI1 lower
b01.07
limit%
AI1
higher
b01.08
limit
AI1
higher
b01.09
limit%
Restart
after
b01.16
power on
Control
b01.17
Mode
PID
source
b02.00
selection
PID
feedback
b02.01
source
selection
PID
Output
b02.02
Characte
ristic
Setting
Factory
Recommend
Range
Setting
-ed Setting
0-100
10 bar
bar
0-10V
1.0V
-100 to
0%
100
0-10V
5V
-100 to
100%
100
0-1
1
0-1
1
0-1
0
0-1
0
0-1
0
Description
For example, if the rated range of
transducer is 0-10 bar, b01.05
should be set to 10.0
10 bar
Lower limit settings should not be
1.0V
changed unless transducer is not 4-
20mA Current Type nor 0-10V
Voltage Type.
0%
4-20mA pressure transducer
requires setting of b01.06=1V and
5V
b01.08=5V. When the displayed
pressure is less than the pressure
gauge reading, increase b01.08
and when the displayed pressure is
100%
greater than pressure gauge
reading, decrease b01.08.
0: Invalid
1
Allows unattended management
0: Synchronous
1
1: Master Slave
0: Keypad
0
0: AI1
0
0: Water supply 1:Pumping
0
22
1: Valid
1:Reserved
1:Reserved