6.9 Pumping Application
System Wiring
In diagram;
(1) Pumpverter
(2) Pumps
(3) Water Level Transmitter. Transmitter used is 4-20mA current type. Jumper for
AI1 (J19) set to current feedback signal selection I, refer to figure 1
Used in environmentally friendly sewage treatment, water level control, drainage and
irrigation etc. Water level above 40%, Pumping in full frequency; below 40%, slow
pumping; below 10% stop pumping
Relevant Parameter Setting
Factory
Code
Recommended
Setting
b00.00 65535
b08.01
~
b08.05
b00.02
0
Pumpverter
Figure 12 Pumping control wiring
Password of entering parameter groups. Factory set is
65535
65535, it can be modified by b06.09
To ensure normal operation, must input parameter
according to motor nameplate
Motor rotating direction, set according to the actual
x
motor wiring. Make sure the motor is running in
forward direction
Description
6 31