5. INVERTER PARAMETERS DESCRIPTION
Function
Name
Code
Debugging
b00.00
Password
Pressure Setting
b00.01
Valve
Motor Rotating
b00.02
Direction
Anti-clogging
b00.04
Anti-clogging
b00.05
Rotating Cycle
Anti-clogging
Output
b00.06
Frequency
High Water
Pressure/Level
b01.00
Alarm Value
Low Water
Pressure/Level
b01.01
Alarm Value
Low Pressure/
Level Alarm
b01.02
Running Time
Minimum
Freeze Proofing
b01.03
Frequency
Anti-clogging
FWD/REV
b01.04
Dead Time
Maximum
Transducer
b01.05
Setting Range
Factory
Setting Range
Setting
0~65535
65535
0.0~100bar 3.0bar
0~1
0~1
1~300s
20.0s
0~600
15.0Hz
Hz
0.0~100.0
8.0bar
bar
0.0~100.0
0.5bar
bar
0~300s
20s
1.00-30.00
5.00Hz
Hz
0.0~3600s
1.0s
0.0~100.0
10.0bar
bar
4 9
Set at b06.09, default is 65535
S e t a c c o r d i n g t o t h e a c t u a l
requirements
0: Forward
0
Ensure pump motor is running
correctly
Prevention measures
0
0: Invalid
Set the forward/reverse rotating
direction cycle and corresponding
output frequency of anti-clogging
(should not be higher than the rated
frequency of the pump).
When pressure is higher than the
preset value, the controller will stop
show alarms and display HP
When the pressure is lower than the
preset value for the low pressure
running time, the controller will stop,
show alarms and displays LP
Be valid when b00.03 was set to 1,
whenever sleeps, running with the
setting frequency in case of freezing
When anti clogging is valid, b01.04
sets the FWD/REV transition time
E.g. If the rated max. range of
transducer is 10bar, b01.05 should
be set to 10.0
Description
1: Reverse
1: Valid