DAYLIFF PVm015 Installation & Operating Manual page 29

Pumpverter vfd controller

Advertisement

Relevant Parameter Setting
Follow section 6.4 to set other parameters first and then refer to this application to set
day part control parameters.
Factory
Code
Recommended
Setting
b01.11
b01.13
b07.00
0
00-00
b07.01
3.0
b07.02
b07.03
00-00
2.0
b07.04
00-00
b07.05
b07.06
3.0
b07.07
00-00
b07.08
2.0
b07.09
00-00
b07.10
3.0
00-00
b07.11
2.0
b07.12
0.0
b07.13
b00.01
3.0
Inlet transducer calibration (b01.11,b01.13), if need
not detect inlet pressure, do not install inlet transducer
but the inlet pressure lower limit of every day-part must
be set as 0 is needed.
Day-part number setting, 0 means day-part control
3
invalid, proceed to choose 3 day part
Set 00:00~06:00 running with 2.5bar stop when inlet
00-00
pressure
2.5
Below 2.0bar (It recovers running when inlet pressure
06-00
return to 2.0bar again)
2.0
06-00
3.2
Set 06:00~13:30 running with 3.2bar, stop when
inlet pressure below 2.3bar
13-30
2.3
17-00
Set 17:00~23:00 running with 3.5bar, stop when
3.5
inlet pressure below 2.2bar
23-00
2.2
Set running with 3.0bar at the undefined time, stop
1.8
when inlet pressure below 1.8bar
3.0
Description
27