Relevant Parameter Setting
Follow section 6.4 to set other parameters first and then refer to this application to set
day part control parameters.
Factory
Code
Recommended
Setting
b01.11
b01.13
b07.00
0
00-00
b07.01
3.0
b07.02
b07.03
00-00
2.0
b07.04
00-00
b07.05
b07.06
3.0
b07.07
00-00
b07.08
2.0
b07.09
00-00
b07.10
3.0
00-00
b07.11
2.0
b07.12
0.0
b07.13
b00.01
3.0
Inlet transducer calibration (b01.11,b01.13), if need
not detect inlet pressure, do not install inlet transducer
but the inlet pressure lower limit of every day-part must
be set as 0 is needed.
Day-part number setting, 0 means day-part control
3
invalid, proceed to choose 3 day part
Set 00:00~06:00 running with 2.5bar stop when inlet
00-00
pressure
2.5
Below 2.0bar (It recovers running when inlet pressure
06-00
return to 2.0bar again)
2.0
06-00
3.2
Set 06:00~13:30 running with 3.2bar, stop when
inlet pressure below 2.3bar
13-30
2.3
17-00
Set 17:00~23:00 running with 3.5bar, stop when
3.5
inlet pressure below 2.2bar
23-00
2.2
Set running with 3.0bar at the undefined time, stop
1.8
when inlet pressure below 1.8bar
3.0
Description
27