Programming menu

To get into this menu you need to insert a 4 level password (default one is 44444) enabling hardware
programming key on the front panel (J1 jumper in A position, see installation manual, "Front board mapping"
chapter).
To insert the password see editing function explained in "keyboard operation for data insertion" paragraph.
Choosing "Program" sub-menu, the following parameters can be configured:
Where:
 Loop configuration (Loop conf.)
Allows, for each zone, integrated module address programming whereas UDS-3 was connected to analog
control panels through addresses from 10 to 90, ten by ten.
It's also possible to enable/disable each MMX module management
 Password
It allows setting different access level passwords.
N.B.:
Default passwords are the following:
2 level password = 22222
3 level password = 33333
4 level password = 44444
 Release
For each zone the following must be performed:
-
Extinguishing output activation time programming
-
Flowmeter control enabled/disabled
-
Flowmeter and manostat input programming (NC or NO in standby mode)
PAGE - 20
NOTIFIER ITALIA
Installation and operating manual
Doc. M-205.1-UDS3N-ENG Rev A.1
See Loop Configuration paragraph
See Password paragraph
See Extinguishing paragraph
Starting address programming.
N.B.: using 00 address analog
line signalling is completely
disabled
Enabling/disabling single modules
NO = Disabled
YES = Enabled
UDS-3