Enabling flowmeter control (Flow ctrl.: YES)
This input activation indicates that extinguishing release is in progress.
If flowmeter output activates during standby condition, it means that extinguishing has not been
started by UDS-3 panel but by an external device (for example a manual activation of the rapid flow
valve). This brings UDS-3 into "release condition". If, instead, UDS-3 starts release condition, this input
is used to manage release cycle.
If "Flow ctrl.: NO" the panel controls only manostat input.

Configuration Menu

Selecting "Config" menu (with level 3 password) you can access the following configuration parameters:
UDS Version
Shows firmware version and configuration
menu. Configuration parameter is a
number that increases each time a new
set of changes is performed (except
password).
PAGE - 21
NOTIFIER ITALIA
Release delay (Rel. delay)
For each zone i
automatic release (that can go from 0 to 60 seconds
with 5 sec steps) and pre-release delay for manual
release (that can go from 0 to 5 seconds with 1 sec
steps)
Reset delay
For each zone it allows to set inhibition time for reset in case a
release alarm condition was present.
If enabled, delay can go from 1 to 30 minutes with 1 minute
steps. This function can be useful to avoid to an operator to block
release in progress with an extended timing.
Installation and operating manual
Doc. M-205.1-UDS3N-ENG Rev A.1
Extinguishing output activation time programming.
You can set the following timings:
2 seconds
60 seconds
150 seconds
10 minutes
t allows to set pre-release time for
UDS-3
UDS-3_manu