Manual mode menu

Selecting "Manual mode" sub-menu (with 2 level password) it's possible to access "MANUAL" or "AUTOMATIC"
modes settings for each zone.
Test menu
It allows accessing the following topics:
-
Led
-
Display

Utilities menu

This function allows (with level 3 password) date and time programming for UDS-3 control panel.
PAGE - 22
NOTIFIER ITALIA
Manual mode selection makes it possible to activate
extinguishing system only with a signal coming from a
manual activation. This condition can also be activated
enabling an input on the terminal board (only manual
extinguishing input).
In this condition UDS-3 only manages signals coming from
"Manual activation" input, other pre-activation/activation
signals are ignored.
This mode is also shown by:
"Only manual mode" led ON
Common warning relay output activation
Manual mode activation indication in extinguishing
information screen
Installation and operating manual
Doc. M-205.1-UDS3N-ENG Rev A.1
LED
Selecting with arrow keys
pressing enter key
to confirm, UDS-3
performs lamp-test (all panel's led blink for a
few seconds)
DISPLAY
Selecting with arrow keys
pressing enter key
to confirm, UDS-3
performs display test
Date programming
Time programming
lamp voice and
display voice and
UDS-3
UDS-3_manu