ABSORPTION CALCULATION
CONTROL PANEL
UDS-3
Sounder output connected
devices
Pre-alarm output connected
devices
Release fault output
connected devices
Discharge done output
connected devices
Directional valves output
connected devices
Release output connected
devices
Analog loop 1 (if enabled)
Analog loop 2 (if enabled)
User output current
Bells
Sounders
Blinking lights
Other loads
Check that the load for each output is in the allowed limits
Refer to devices' producer data sheets to know necessary current in standby and working mode. Check
that current is less than 1,55 Ampere.
Current absorption for standby or alarm can't be more than power supply capacity in any case. If
calculated current is more than 1.55 Ampere (supplied by power supply unit) excess current is retrieved
by batteries.
Sum of all currents obtained must be multiplied per 1.25 to take into consideration batteries'
manufacturing tolerances.
PAGE - 38
NOTIFIER ITALIA
Standby condition
A
Consumption
0.100
0.0025
0.0025
(Max 1.25 A )
0
0
0
|_________|
|_________|
Total
=
x 24 h =
Stand-by (A)
Ah Battery = (A + B) x 1.25 =
Installation and operating manual
Doc. M-205.1-UDS3N-ENG Rev A.1
Active condition
B
Consumption
One zone = 0.220
Two zones = 0.300
0
|_________|
0
|_________|
0
0
|_________|
0
|_________|
0
|_________|
(Max 1.25 A )
0
|_________|
|_________|
0
|_________|
|_________|
0
|_________|
|_________|
|_________|
|_________|
Total
=
x 0.5 h =
Alarm (B)
Ah
0.0025
0.0025
Ah
Ah
UDS-3
UDS-3_manu