CNZ1
Zone 1 connections
1
Alarm input 1
2
GND
3
Alarm input 2
4
Manual extinguishing activation input
5
GND
6
Emergency delay input
7
"Only manual" extinguishing input
8
GND
9
Emergency interruption device input
10
Manostat input
11
GND
12
Flowmeter input
13
Pre-alarm output LC –
14
Pre-alarm output LC +
15
Sounder output LC -
16
Sounder output LC +
17
Extinguishing Plant fault output/zone 1
excluded LC-
18
Extinguishing Plant fault output/zone 1
excluded LC+
Discharge-finished relay NO-NC
19
Discharge-finished relay C
20
21
Pilot cylinder output / directional valve LC-
22
Pilot cylinder output / directional valve LC+
23
Extinguishing output LC-
24
Extinguishing output LC+
N.B.:
polarities shown in the table are referred to UDS-3 panel stand-by condition
All controlled outputs are protected by a 0,65A self-restorable fuse.
PAGE - 6
NOTIFIER ITALIA
Notes
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 23)
Termination resistance 2,7K (for connections see p. 26)
Termination resistance 2,7K (for connections see p. 25)
Termination resistance 2,7K (for connections see p. 27)
JRL12 (Jumper for output contact selection).
Contact capacity: 1A - 24Vdc resistive
N.B.: do NOT connect to this output remote commands
like telephone diallers because this output is not
controlled
Termination resistance 2,7K (for connections see p. 28)
Termination resistance 2,7K (for connections see p. 24)
Installation and operating manual
Doc. M-205.1-UDS3N-ENG Rev A.1
UDS-3