Allen-Bradley Micro800 2080-MEMBAK-RTC2 User Manual page 87

Plug-in modules
Table of Contents

Advertisement

Rockwell Automation Publication 2080-UM004D-EN-E - March 2018
Maximum output currrent per point – 5V DC operation
Current Derating Based on Temperature
1.5
1
0.5
0
-20
-10
0
10
Ambient Temperature (°C)
Maximum output current per point – 24V DC operation
Current derating based on temperature
1.5
1
0.5
0
-20
-10
0
10
Ambient temperature (°C)
Environmental Specifications – 2080-MOT-HSC
Attribute
Temperature, operating
Temperature, nonoperating
Temperature, surrounding air,
max
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
Emissions
ESD immunity
20
30
40
50
60
20
30
40
50
60
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4...149 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40...185 °F)
65 °C (149 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
35 g (PANEL mount)
CISPR 11 (IEC 61000-6-4):
Class A
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Specifications Appendix A
70
70
77