Allen-Bradley Micro800 2080-MEMBAK-RTC2 User Manual page 90

Plug-in modules
Table of Contents

Advertisement

Appendix A
Specifications
80
ATTENTION: To comply with UL restrictions, this equipment must be
powered from a source compliant with the following: Class 2 or Limited
Voltage/Current.
Environmental Specifications – 2080-DNET20
Attribute
Temperature, operating
Temperature, surrounding air,
max.
Temperature, nonoperating
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
Emissions
ESD Immunity
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4...149 °F)
65 °C (149 °F)
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
2g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
35 g (PANEL mount)
CISPR 11 (IEC 61000-6-4):
Class A
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4:
±2 kV @ 5 kHz on communication ports
IEC 61000-4-5:
±2 kV line-earth(CM) on communication ports
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Rockwell Automation Publication 2080-UM004D-EN-E - March 2018

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Micro800 2080-iq4ob4Micro800 2080-iq4ov4Micro800 2080-ob4Micro800 2080-ov4Micro800 2080-ow4iMicro800 2080-if2 ... Show all

Table of Contents