Non-isolated Thermocouple and RTD Plug-in Modules – 2080-TC2 and 2080-RTD2
It supports two- and three-wire type of RTD sensor wiring.
RTD Compatibility
An RTD consists of a temperature-sensing element connected by two, three, or
four wires that provide resistance input to the module. The following table lists
the RTD types that you can use with the module, including their temperature
range, accuracy, and ADC update rate.
Overrange and Underrange Conditions
If the channel temperature input is below the minimum value of its normal
temperature range for the represented sensor, the module reports an underrange
error through the Connected Components Workbench global variables. If the
channel temperature input is above the maximum value of its normal temperature
range for the represented sensor, an over-range error is flagged.
RTD Sensor Types and Temperature Ranges
RTD Type
Temperature
Range ° C (°F)
Min
PT100 385
-200
660
(-328)
(1220)
PT200 385
-200
630
(-328)
(1166)
PT500 385
-200
630
(-328)
(1166)
PT1000 385
-200
630
(-328)
(1166)
PT100 392
-200
660
(-328)
(1220)
PT200 392
-200
630
(-328)
(1166)
PT500 392
-200
630
(-328)
(1166)
PT1000 392
-50
500
(-58)
(932)
(1)
Cu10 427
-100
260
(-148)
(500)
Ni120 672
-80
260
(-112)
(500)
NiFe604 518
-200
200
(-328)
(392)
(1) For Cu10 427, accuracy range is within >±1.0 < ±3.0 for -70...220 °C (-94...428 °F). Above this temperature
range, it is > ±3.0 °C as shown in the table.
Accuracy ° C (°F)
Max
±1.0 °C
±3.0 °C
-150...590
< -150 (-238)
(-238...1094)
> 590 (1094)
-150...570
< -150 (-238)
(-238...1058)
> 570 (1058)
-150...580
< -150 (-238)
(-238...1076)
> 580 (1076)
-150...570
< -150 (-238)
(-238...1058)
> 570 (1058)
-150...590
< -150 (-238)
(-238...1094)
> 590 (1094)
-150...570
< -150 (-238)
(-238...1058)
> 570 (1058)
-150...580
< -150 (-238)
(-238...1076)
> 580 (1076)
-20...450
< - 20 (-4)
(-4...842)
> 450 (842)
< -70 (-94)
> 220 (428)
-50...220
< -50 (-58)
(-58...428)
> 220 (428)
-170...170
< -170 (-274)
(-274...338)
> 170 (338)
Chapter 3
ADC Update
Rate in Hz
(Accuracy °C)
3-wire others
4.17, 6.25, 10, 16.7,19.6,
33, 50 (±1.0)
62, 123, 242, 470 (±3.0)
(1)
2- and 3-wire Cu10
4.17, 6.25, 10, 16.7
(>±1.0 < ±3.0)
19.6, 33, 50, 62, 123, 242,
470 (> ±3.0)
2-wire others
4.17, 6.25, 10, 16.7 (±1.0)
19.6, 33, 50, 62, 123, 242,
470 (±3.0)