Chapter 5
DeviceNet Plug-in – 2080-DNET20
Dual Source Power Supply (both ends – Kwiklink Lite Cable)
9.00
8.00
7.00
6.00
5.00
4.00
3.00
2.00
1.00
0.00
40
80
0 (0)
(131)
(262)
46
Single Source Power Supply – Trunkline Length and Maximum Current
120 (394)
2.39
140 (459)
2.05
160 (525)
1.79
180 (591)
1.60
200 (656)
1.44
(1) Exceeds NEC CL2/CECode 4A limit.
120
160
200
(394)
(525)
(656)
Dual source power supply (both ends – Kwiklink Lite Cable)
Network length
Current, max
in meters (ft)
0 (0)
8.00
20 (66)
8.00
40 (131)
8.00
60 (197)
8.00
80 (262)
8.00
100 (328)
8.00
120 (394)
8.00
140 (459)
7.35
160 (525)
6.43
180 (591)
5.72
200 (656)
5.16
(1) Exceeds NEC CL2/CECode 4A limit.
340 (1115)
0.85
360 (1181)
0.80
380 (1247)
0.76
400 (1312)
0.72
420 (1378)
0.69
320
280
240
(1050)
(787)
(919)
Network length
in meters (ft)
(1)
220 (722)
240 (787)
260 (853)
280 (919)
300 (984)
320 (1050)
340 (1115)
360 (1181)
380 (1247)
400 (1312)
420 (1378)
Rockwell Automation Publication 2080-UM004D-EN-E - March 2018
400
360
(1312)
(1181)
Current, max
4.69
4.30
3.97
3.69
3.44
3.23
3.04
2.87
2.72
2.59
2.46