Specifications
66
Environmental Specifications – 2080-OW4I
Attribute
Temperature, operating
Temperature, surrounding air,
max.
Temperature, non-operating
Relative humidity
Vibration
Shock, operating
Shock, non-operating
ESD Immunity
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Value
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4...149 °F)
65 °C (149 °F)
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
10 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN rail mounting: 25 g
Panel mounting: 35 g
IEC 61000-4-2:
6kV contact
8 kV air
IEC 61000-4-3
10 V/M with 1 kHz sine-wave 80%AM from 80...2000 MHz
10 V/M with 200 Hz sine-wave 50% Pulse 100%AM @ 900 MHz
10 V/M with 200 Hz sine-wave 50% Pulse 100%AM @1890 MHz
10 V/M with 1 kHz sine-wave 80%AM from 2000...2700 MHz
IEC 61000-4-4:
±2 kV @ 5 kHz on signal ports
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz