Allen-Bradley Micro800 2080-MEMBAK-RTC2 User Manual page 74

Plug-in modules
Table of Contents

Advertisement

Appendix A
Specifications
64
General Specifications – 2080-OW4I Digital Relay Output Plug-in Module
Attribute
North American temp code
Inrush current
Backplane power
Output current, resistive
Output current, inductive
Output power, resistive, max
Pilot duty rating
Minimum load, per point
Initial contact resistance of
relay, max
Output delay time, max
Relay Contact Ratings (0.35 power factor) – 2080-OW4I
Maximum Volts
Amperes
Make
120V AC
15 A
240V AC
7.5 A
24V DC
1.0 A
125V DC
0.22 A
Value
T4
<120 mA @ 3.3V
<120 mA @ 24V
3.3 VDC, 38 mA
2 A @ 5...30V DC
0.5 A @ 48V DC
0.22 A @ 125V DC
2 A @ 125V AC
2 A @ 240V AC
1.0 A steady state @ 5...28V DC
0.93 A steady state @ 30V DC
0.5 A steady state @ 48V DC
0.22 A steady state @ 125V DC
2.0 A steady state, 15 A make @ 125V AC, PF – cos θ = 0.4
2.0 A steady state, 7.5 A make @ 240V AC, PF – cos θ = 0.4
250 VA for 125V AC resistive loads
480 VA for 240V AC resistive loads
60 VA for 30V DC resistive loads
24 VA for 48V DC resistive loads
27.5 VA for 125V DC resistive loads
C300, R150
10 mA
30 mΩ
10 ms ON or OFF
Amperes
Continuous
Break
1.5 A
2.0 A
0.75 A
Rockwell Automation Publication 2080-UM004D-EN-E - March 2018
Volt-Amperes
Make
Break
1800 VA
180 VA
28 VA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Micro800 2080-iq4ob4Micro800 2080-iq4ov4Micro800 2080-ob4Micro800 2080-ov4Micro800 2080-ow4iMicro800 2080-if2 ... Show all

Table of Contents