Allen-Bradley Micro800 2080-MEMBAK-RTC2 User Manual page 55

Plug-in modules
Table of Contents

Advertisement

Single Source Power Supply (End segment) Kwiklink Lite Cable
9.00
8.00
7.00
6.00
5.00
4.00
3.00
2.00
1.00
0.00
60
0 (0)
(197)
Rockwell Automation Publication 2080-UM004D-EN-E - March 2018
If two or more power supplies are connected to the Kwinklink lite media (trunk
cable) V+ should be broken between the two power supplies.
CAN_H
CAN_L
V-
V+
V-
Power Supply
only one ground
Grounding the network
TIP
If grounding at only one location, it is recommended that you ground at the
center of the network.
120
180
(394)
(591)
Single Source Power Supply – Trunkline Length and Maximum Current
Network Length
Current, max
in meter (ft)
(1)
0 (0)
8.00
(1)
20 (66)
8.00
(1)
40 (131)
7.01
(1)
60 (197)
4.72
80 (262)
3.56
100 (238)
2.86
DeviceNet Plug-in – 2080-DNET20
V+ broken between
V+
power supplies
Enclosure
240
300
(787)
(984)
Network Length
in meter (ft)
220(722)
240 (787)
260 (853)
280 (919)
300 (984)
320 (1050)
V-
V+
Power Supply
360
420
(1181)
(1378)
Current, max
1.31
1.20
1.11
1.03
0.96
0.90
Chapter 5
45