Daikin EPRA10EAV3 Installer's Reference Manual page 297

Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
9.I
[1-0A]
What is the averaging time for the outdoor temp?
9.I
[1-0B]
What is the desired delta T in heating for the main zone?
9.I
[1-0C]
What is the desired delta T in heating for the additional zone?
9.I
[1-0D]
What is the desired delta T in cooling for the main zone?
9.I
[1-0E]
What is the desired delta T in cooling for the additional zone?
9.I
[2-00]
When should the disinfection function be executed?
9.I
[2-01]
Should the disinfection function be executed?
9.I
[2-02]
When should the disinfection function start?
9.I
[2-03]
What is the disinfection target temperature?
9.I
[2-04]
How long must the tank temperature be maintained?
9.I
[2-05]
Room antifrost temperature
9.I
[2-06]
Room frost protection
9.I
[2-09]
Adjust the offset on the measured room temperature
9.I
[2-0A]
Adjust the offset on the measured room temperature
9.I
[2-0B]
What is the required offset on the measured outdoor temp.?
9.I
[2-0C]
What emitter type is connected to the main LWT zone?
9.I
[2-0D]
What emitter type is connected to the additional LWT zone?
9.I
[2-0E]
What is the maximum allowed current over the heatpump ?
9.I
[3-00]
Is auto restart of the unit allowed?
9.I
[3-01]
--
9.I
[3-02]
--
9.I
[3-03]
--
9.I
[3-04]
--
9.I
[3-05]
--
9.I
[3-06]
What is the maximum desired room temperature in heating?
9.I
[3-07]
What is the mimimum desired room temperature in heating?
9.I
[3-08]
What is the maximum desired room temperature in cooling?
9.I
[3-09]
What is the minimum desired room temperature in cooling?
9.I
[3-0A]
What is the pump model
9.I
[4-00]
What is the BUH operation mode?
9.I
[4-01]
Which electric heater has priority?
9.I
[4-02]
Below which outdoor temperature is heating allowed?
9.I
[4-03]
Operation permission of the booster heater.
9.I
[4-04]
Water pipe freeze prevention
9.I
[4-05]
--
9.I
[4-06]
Emergency
9.I
[4-07]
--
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) EKECBUA3V_(*7) EKECBUA6V_(*8) EKECBUA9W_
(*9) BUH less
Range, step
Default value
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
[2-0C]≠2:
3~10°C, step: 1°C
R/W
[2-0C]≠2 (Radiator):
[2-0C]=2:
5°C
R/O
[2-0C]=2 (Radiator):
10°C
[2-0D]≠2:
[2-0D]≠2 (Radiator):
R/W
3~10°C, step: 1°C
[2-0D]=2:
5°C
R/O
[2-0D]=2 (Radiator):
10°C
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0: No
1: Yes
R/W
0~23 hour, step: 1 hour
1
R/W
60°C
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
4~16°C, step: 1°C
8°C
R/W
0: Disabled
1: Enabled
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
20~50 A, step: 1 A
50 A
R/W
0: No
1: Yes
R/W
0
R/W
1
R/W
4
R/W
2
R/W
1
R/W
18~30°C, step: 1°C
30°C
R/W
12~18°C, step: 1°C
12°C
R/W
25~35°C, step: 1°C
35°C
R/W
15~25°C, step: 1°C
15°C
R/O
0: pump model 0
1: pump model 1
R/W
0: Disabled
1: Enabled
2: Only DHW
R/W
0: None
1: BSH
2: BUH
R/W
14~35°C, step: 1°C
35°C
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
R/W
0: Continuous pump operation
1: Non continuous pump operation
2: OFF
0
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
3
9/13
Installer setting at variance with
default value
Date
Value
4P670987-1A - 2022.02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents