Field settings table
Breadcrumb
Field code
Setting name
9.6.3
[5-04]
Offset BSH setpoint
9.6.4
[8-02]
Anti-recycle timer
9.6.5
[8-00]
Minimum running timer
9.6.6
[8-01]
Maximum running timer
9.6.7
[8-04]
Additional timer
Installer settings
9.7
[4-04]
Water pipe freeze prevention
└─ Benefit kWh power supply
9.8.2
[D-00]
Allow heater
9.8.3
[D-05]
Allow pump
9.8.4
[D-01]
Benefit kWh power supply
9.8.6
Allow electric heaters
9.8.7
Enable Room buffering
9.8.8
Limit setting kW
└─ Power consumption control
9.9.1
[4-08]
Power consumption control
9.9.2
[4-09]
Type
9.9.3
[5-05]
Limit
9.9.4
[5-05]
Limit 1
9.9.5
[5-06]
Limit 2
9.9.6
[5-07]
Limit 3
9.9.7
[5-08]
Limit 4
9.9.8
[5-09]
Limit
9.9.9
[5-09]
Limit 1
9.9.A
[5-0A]
Limit 2
9.9.B
[5-0B]
Limit 3
9.9.C
[5-0C]
Limit 4
9.9.D
[4-01]
Priority heater
9.9.F
[7-07]
BBR16 activation*
*BBR16 settings are only visible when the language of the user interface is set to
Swedish.
└─ Energy metering
9.A.1
[D-08]
Electricity meter 1
9.A.2
[D-09]
Electricity meter 2 / PV meter
└─ Sensors
9.B.1
[C-08]
External sensor
9.B.2
[2-0B]
Ext. amb. sensor offset
9.B.3
[1-0A]
Averaging time
└─ Bivalent
9.C.1
[C-02]
Bivalent
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*6) EKECBUA3V_(*7) EKECBUA6V_(*8) EKECBUA9W_
(*9) BUH less
Range, step
Default value
R/W
0~20°C, step: 1°C
10°C
R/W
0~10 hour, step: 0,5 hour
0,5 hour
R/O
0~20 min, step 1 min
1 min
R/W
5~95 min, step: 5 min
30 min
R/W
0~95 min, step: 5 min
95 min
R/W
0: Continuous pump operation
1: Non continuous pump operation
2: OFF
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
R/W
0: Forced off
1: As normal
R/W
0: No
1: Active open
2: Active closed
3: Smart Grid
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
0~20 kW, step: 0,5 kW
2 kW
R/W
0: No limitation
1: Continuous
2: Digital inputs
3: Load Monitor
R/W
0: Current
1: Power
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
0: None
1: BSH
2: BUH
R/W
0: Disabled
1: Enabled
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
8 1 pulse/m³ (gas monitoring)
9 10 pulse/m³ (gas monitoring)
10 100 pulse/m³ (gas monitoring)
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
0 none
1 bivalent through header
2 tank DHW bivalent (*5)
3 tank heating + DHW bivalent
7/13
Installer setting at variance with
default value
Date
Value
4P670987-1A - 2022.02