Daikin EPRA10EAV3 Installer's Reference Manual page 120

Table of Contents

Advertisement

9
|
Electrical installation
Installer reference guide
120
A
2x
a
230
V AC
1N~, 50 Hz,
1 2 3
A
B
B
a Interconnection cable
b Power supply indoor unit
In case of preferential kWh rate power supply
Interconnection cable Wires: (3+GND)×1.5 mm²
Power supply indoor
unit
Preferential kWh rate
power supply contact
[9.8] Benefit kWh power supply
F2B
, 6.3 A
Q DI
2
L
1
2
N
3
4
a
b
X1M
1 2 3 4 5 6
Wires: 1N+GND
Maximum running current: 6.3 A
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply contact:
16 V DC detection (voltage supplied by PCB). The
voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
b
5
6
2x
EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents