Daikin Altherma 3 H MT ECH2O Installer's Reference Manual

Daikin Altherma 3 H MT ECH2O Installer's Reference Manual

Hide thumbs Also See for Altherma 3 H MT ECH2O:
Table of Contents

Advertisement

EPRA08EAV3
EPRA10EAV3
EPRA12EAV3
EPRA08EAW1
EPRA10EAW1
EPRA12EAW1
Installer reference guide
Daikin Altherma 3 H MT ECH₂O
https://daikintechnicaldatahub.eu
ETSH12P30EF
ETSH12P50EF
ETSHB12P30EF
ETSHB12P50EF
ETSX12P30EF
ETSX12P50EF
ETSXB12P30EF
ETSXB12P50EF

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma 3 H MT ECH2O

  • Page 1 Installer reference guide Daikin Altherma 3 H MT ECH₂O https://daikintechnicaldatahub.eu EPRA08EAV3 ETSH12P30EF EPRA10EAV3 ETSH12P50EF EPRA12EAV3 ETSHB12P30EF ETSHB12P50EF EPRA08EAW1 ETSX12P30EF EPRA10EAW1 ETSX12P50EF EPRA12EAW1 ETSXB12P30EF ETSXB12P50EF...
  • Page 2: Table Of Contents

    Power limitation activated by digital inputs ....................61 6.6.3 Power limitation process..........................63 6.6.4 BBR16 power limitation..........................63 Setting up an external temperature sensor ........................64 Installer reference guide EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 3 To connect the WLAN cartridge (delivered as accessory)................138 9.3.15 To connect the solar input ..........................139 9.3.16 To connect the DHW output .......................... 139 EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 4 Symptom: The pressure relief valve opens....................254 14.3.8 Symptom: The water pressure relief valve leaks................... 254 14.3.9 Symptom: The space is NOT sufficiently heated at low outdoor temperatures........... 254 Installer reference guide EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 5 Wiring diagram: Indoor unit ............................279 16.6 ESP curve: Indoor unit..............................285 16.7 Name plate: Indoor unit ..............................285 17 Glossary 18 Field settings table EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 6: About The Documentation

    Format: Paper (in the box of the indoor unit) + Digital files on http:// www.daikineurope.com/support-and-manuals/product-information/ Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer. The original documentation is written in English. All other languages are translations. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O...
  • Page 7: Meaning Of Warnings And Symbols

    About the documentation Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
  • Page 8: Installer Reference Guide At A Glance

    General safety precautions Safety instructions that you must read before installing Specific installer safety instructions About the box How to unpack the units and remove their accessories EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 9 Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 10: General Safety Precautions

    Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
  • Page 11: Installation Site

    Make sure the field piping and connections are NOT subjected to stress. WARNING During tests, NEVER pressurise the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 12 ONLY use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system. ▪ Charge the liquid refrigerant as follows: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 13: Water

    If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 14 Install power cables at least 1  meter away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1  meter may NOT be sufficient. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 15 ON and OFF while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 16: Specific Installer Safety Instructions

    The appliance shall be stored so as to prevent mechanical damage and in a well- ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 17 Specific installer safety instructions WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. Mounting the outdoor unit (see "7.3 Mounting the outdoor unit" [  75]) WARNING Fixing method of the outdoor unit MUST be in accordance with the instructions from this manual.
  • Page 18 ▪ Make electrical connections to the fixed wiring. ▪ All components procured on-site and all electrical construction MUST comply with the applicable legislation. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 19 This maximum allowable hot water temperature shall be selected according to the applicable legislation. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 20 If yes, make sure that the room where you want to purge air is sufficiently ventilated. Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 21: About The Box

    To avoid injury, do NOT touch the air inlet or aluminium fins of the unit. Crane Keep the slings within the marked area to not damage the unit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 22 After unpacking, carry the unit using the slings attached to the unit. See also: ▪ "4.2.2 To unpack the outdoor unit" [  23] ▪ "7.3.4 To install the outdoor unit" [  76] ±120 4× EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 23: To Unpack The Outdoor Unit

    About the box 4.2.2 To unpack the outdoor unit EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 24: To Remove The Accessories From The Outdoor Unit

    ▪ Bring the packed unit as close as possible to its final installation position to prevent damage during transport. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 25: To Unpack The Indoor Unit

    Drain pan hose clamp l Cable fixation for strain relief m Cable tie n Switch box metal insert o Screw for switch box metal insert EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 26: To Handle The Indoor Unit

    3 Use the handles to carry the unit. 4 After carrying the unit remove the handles, add the screw plugs again and insert the thread covers on the plugs. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 27: About The Units And Options

    Explanation European hydro-split outdoor pair heat pump High water temperature – ambient zone 2 (see operation range) Refrigerant R32 Capacity class Model series Power supply EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 28: Identification Label: Indoor Unit

    Certain options may NOT be available in your country. 5.3.1 Possible combinations of indoor unit and outdoor unit Indoor unit Outdoor unit EPRA08 EPRA10 EPRA12 ETSH/X EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 29: Possible Options For The Outdoor Unit

    As an option the remote indoor sensor can be installed to measure the room temperature on another location. For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 30 Bizone kit (EKMIKPOA or EKMIKPHA) You can install an optional bizone kit. For installation instructions, see the installation manual of the bizone kit. See also: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 31 For installation instructions, see the installation manual of the recirculation kit. Dirt Separator (156021 or 156023) It is recommended to install a dirt separator in the system. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 32 A solar drainback kit including solar pump and solar controller can be directly connected to the pressureless storage tank of the indoor unit. For installation instructions, see the installation manual of the solar drainback kit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 33: Application Guidelines

    Setting up the storage tank ▪ Setting up the energy metering ▪ Setting up the power consumption control ▪ Setting up an external temperature sensor EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 34: Setting Up The Space Heating/Cooling System

    Automatic. NOTICE An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 35: Single Room

    For your daily needs, you can use preset values and schedules. To deviate from your daily needs, you can temporarily overrule the preset values and schedules, or use the holiday mode. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 36 Code: [C-05] heating or cooling demand. Benefits ▪ Wireless. The Daikin external room thermostat is available in a wireless version. ▪ Efficiency. Although the external room thermostat only sends ON/OFF signals, it is specifically designed for the heat pump system. ▪...
  • Page 37 ON/ ▪ #: [2.A] OFF condition. No separation between ▪ Code: [C-05] heating or cooling demand. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 38 ▪ The space operation mode is sent by one digital output (X12M/9 and X12M/10) on the indoor unit to: The heat pump convectors The shut-off valve EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 39: Multiple Rooms - One Lwt Zone

    Human Comfort Interface (BRC1HHDA) or an external room thermostat), while the other rooms are controlled by so-called thermostatic valves, which open or close depending on the room temperature. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 40 Number of water temperature zones: 0 (Single zone): Main ▪ #: [4.4] ▪ Code: [7-02] Benefits ▪ Easy. Same installation as for one room, but with thermostatic valves. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 41 Compared with underfloor heating or radiators for one room: ▪ Comfort. You can set the desired room temperature, including schedules, for each room via the room thermostats. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 42 Code: [C-07] Number of water temperature zones: 0 (Single zone): Main ▪ #: [4.4] ▪ Code: [7-02] Benefits Compared with heat pump convectors for one room: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 43 INFORMATION To increase comfort and performance, we recommend to install the valve kit option EKVKHPC on each heat pump convector. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 44: Multiple Rooms - Two Lwt Zones

    In cooling mode, you can allow the underfloor heating (main zone) to provide refreshment (no real cooling), or NOT allow it. See setup below. Setup Three bizone kit system variations are possible: System without hydraulic separator: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 45 For this system, a direct pump is required for the additional zone. A Additional leaving water temperature zone B Room 1 C Room 2 D Main leaving water temperature zone EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 46 (X12M/19 and X12M/22). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 47 If the main zone must be shut off during cooling mode to prevent condensation on the floor, set it accordingly. "Bizone kit" [  227] for more information on configuration of the bizone kit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 48: Setting Up Bivalent Heat Sources

    Space heating is turned ON, and Tank operation is turned OFF ▪ Domestic hot water is always produced by the storage tank connected to the indoor unit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 49 Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. ▪ Make sure the return water to the heat pump does NOT exceed 60°C. To do so: Set the desired water temperature via the auxiliary boiler controller to maximum 60°C.
  • Page 50 Setpoint of the auxiliary gas boiler To prevent freeze-up of the water piping, the auxiliary gas boiler must have a fixed setpoint ≥55°C, or a weather-dependent setpoint ≥T EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 51: Setting Up An Indirect Auxiliary Heat Source For Domestic Hot Water And Space Heating

    ▪ Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O...
  • Page 52: Setting Up A Solar System Via Drainback Connection

    1 Integrate the solar system as follows: a Drainback solar flow connection (optional solar drainback kit) b Flow sensor (optional solar drainback kit) c Flow rate limiter (optional) d Drainback connection EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 53: Setting Up A Solar System Via Bivalent Heat Exchanger

    For systems without indirect auxiliary boiler connected to the storage tank, it is mandatory to install an electric backup heater to ensure safe operation for all conditions. Configuration Via the user interface (configuration wizard): EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 54: Setting Up The Storage Tank

    Example: If the DHW consumption of a family (4 persons) per day is as follows: ▪ 3 showers ▪ 1 bath ▪ 3 sink volumes Then the DHW consumption = (3×100 l)+(1×150 l)+(3×10 l)=480 l EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 55: Setup And Configuration - Storage Tank

    Bivalent heat source, see "6.3 Setting up bivalent heat sources" [  48] ▪ For more information about optimizing the energy consumption for producing domestic hot water, see "10 Configuration" [  141]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 56: Dhw Pump For Instant Hot Water

    The DHW pump is field-supplied and its installation is the responsibility of the installer. For the electrical wiring, see "9.3.7 To connect the domestic hot water pump" [  126]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 57: Setting Up The Energy Metering

    The flow rate ▪ Setup and configuration: No additional equipment needed. 6.5.2 Consumed energy You can use the following methods to determine the consumed energy: ▪ Calculating EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 58: Normal Kwh Rate Power Supply

    ▪ Three-phase outdoor unit Three-phase ▪ Backup heater supplied from a three- (*9W: 3N~ 400 V) phase grid (i.e. the backup heater model is *9W) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 59: Preferential Kwh Rate Power Supply

    Power meter 2: Measures the rest (i.e. indoor unit and backup heater). Setup ▪ Connect power meter 1 to X15M/5 and X15M/6. ▪ Connect power meter 2 to X15M/9 and X15M/10. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 60: Setting Up The Power Consumption Control

    Allows you to limit the power consumption of the entire heat pump system (sum of indoor unit and backup heater) via 4 digital inputs. ▪ Limitation of power in kW or current in A. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 61: Permanent Power Limitation

    Set the desired power limitation level 6.6.2 Power limitation activated by digital inputs Power limitation is also useful in combination with an energy management system. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 62 Application guidelines The power or current of the entire Daikin system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following: ▪ Current (in A) ▪...
  • Page 63: Power Limitation Process

    (BBR16 activation and BBR16 power limit). After 2 weeks, the unit freezes these settings. Note: This is different from the permanent power limitation, which is always changeable. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 64: Setting Up An External Temperature Sensor

    Setup: For installation instructions, see the installation manual of the remote indoor sensor, and the addendum book for optional equipment. ▪ Configuration: Select room sensor [9.B]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 65 To protect the outdoor unit, the internal sensor of the outdoor unit is always used. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 66: Unit Installation

    Mind the spacing guidelines. See "16.1 Service space: Outdoor unit" [  271]. NOTICE ▪ Do NOT stack the units on each other. ▪ Do NOT hang the unit on a ceiling. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 67 This is to prevent corrosion caused by high levels of salt in the air, which might shorten the life of the unit. Install the outdoor unit away from direct sea winds. Example: Behind the building. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 68 WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O...
  • Page 69: Additional Installation Site Requirements Of The Outdoor Unit In Cold Climates

    Maximum height difference between indoor unit and outdoor 10 m unit Maximum total water piping length between indoor unit and 20 m (single outdoor unit when using 1" piping run) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 70: Opening And Closing The Units

    Precise water piping length can be determined using the Hydronic Piping Calculation tool. The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator which can be reached via https://professional.standbyme.daikin.eu. Please contact your dealer if you have no access to Heating Solutions Navigator.
  • Page 71: To Open The Outdoor Unit

    Keep 4 screws to attach the compressor cover piece (see the installation manual, topic “To attach the compressor cover piece”). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 72: To Close The Outdoor Unit

    User interface panel b Switch box cover Open 1 Remove the user interface panel. Open the hinges at the top and slide the interface panel downwards. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 73: To Lower The Switch Box Of The Indoor Unit And Remove The Top Cover

    Prerequisite: The user interface panel has been removed. 1 Loosen the screws. 2 Lift up the switch box. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 74 4 If necessary, remove the top cover. This is necessary in the following cases: ▪ Connecting water piping ▪ Connecting BIV or DB-kit ▪ Connecting backup heater EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 75: To Close The Indoor Unit

    Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise. Fix the unit securely by means of foundation bolts in accordance with the foundation drawing. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 76: To Install The Outdoor Unit

    Make sure not to cover the drain hole in the bottom plate of the unit. 7.3.4 To install the outdoor unit 1 Carry the unit by its slings, and put it onto the installation structure. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 77: To Provide Drainage

    Install the unit on a base to make sure that there is proper drainage in order to avoid ice accumulation. ▪ Prepare a water drainage channel around the foundation to drain waste water away from the unit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 78 O-ring (delivered as accessory) c Drain plug (delivered as accessory) d Hose (field supply) NOTICE O-ring. Make sure the O-ring is installed correctly to prevent leakage. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 79: To Install The Discharge Grille

    4 Align and attach the left side. 5 Align and attach the middle part. 6 Align and attach the right side. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 80: To Remove The Discharge Grille, And Put The Grille In Safety Position

     79] ▪ "7.3.7 To remove the discharge grille, and put the grille in safety position" [  80] 1 Remove the upper part of the discharge grille. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 81 4 Align the ball stud and hook on the grille with their counterparts on the unit. 5 Insert the hook. 6 Insert the ball stud. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 82: Mounting The Indoor Unit

    Spillover water from the water storage tank as well as water collecting in the drain pan must be drained. You must connect the drain hoses to an appropriate drain according to the applicable legislation. 1 Open the screw plug. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 83 7 Connect the pressure relief valve to an appropriate drain in accordance with the applicable legislation. Ensure that any steam or water that may escape is drained in a frost-protected, safe and observable manner. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 84 Unit installation a Pressure relief valve EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 85: Piping Installation

    Inappropriate tooling will cause damage to the pipes. ▪ Insulation. Insulate up to the base of the heat exchanger. ▪ Freeze. Protect against freezing. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 86 Water temperature. All installed piping and piping accessories (valve, connections,…) MUST withstand the following temperatures: INFORMATION The following illustration is an example and might NOT match your system layout. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 87 Circulation stop valves. We recommend to use circulation stop valves at the connections of the heat exchanger for domestic hot water. This minimizes heat losses due to temperature-induced circulation in the connecting pipes. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 88: To Check The Water Volume And Flow Rate

    NOT included. INFORMATION In critical processes, or in rooms with a high heat load, extra water might be required. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 89: Connecting Water Piping

     235]. 8.2 Connecting water piping 8.2.1 About connecting the water piping Before connecting the water piping Make sure the outdoor and indoor unit are mounted. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 90: Precautions When Connecting The Water Piping

    1") d Thread sealant 2 Connect the field piping to the shut-off valve. 3 Connect the field piping to the outdoor unit water outlet. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 91 ONLY remove parts in the order and direction as indicated here, ▪ do NOT use force, ▪ do NOT use tools, ▪ re-install the thermal insulation in reverse order. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 92 If the space heating/cooling or the domestic hot water pipes are directed upwards, the top cover must be cut along the perforation with a suitable tool. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 93 Domestic cold water IN (cold water supply)(screw connection, 1") e Outdoor unit water OUT (screw connection, 1") f Outdoor unit water IN (screw connection, 1") EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 94: To Connect A Pressure Vessel

    There may not be any hydraulic blocking elements between the heat generator and the safety valve. 2 Position the pressure vessel in an easily accessible place (maintenance, parts replacement). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 95: To Fill The Heating System

    (field supply) to a water tap and the fill and drain valve. Secure the hose against slipping off. 100% Bypass 100% a Hose with a non-return valve (1/2") and an external manometer (field supply) b Fill and drain valve EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 96: To Protect The Water Circuit Against Freezing

    Glycol leaking out of the freeze protection valves. Freeze protection by glycol About freeze protection by glycol Adding glycol to the water lowers the freezing point of water. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 97 Protection against bursting: the glycol will prevent the piping from bursting, but NOT the liquid inside the piping from freezing. ▪ Protection against freezing: the glycol will prevent the liquid inside the piping from freezing. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 98 Note: Leave at least 15 cm clearance from the ground to prevent ice from blocking the water exit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 99: To Fill The Heat Exchanger Inside The Storage Tank

    Before the storage tank can be filled, the heat exchangers inside the storage tank have to be filled, see previous chapters. Fill the storage tank with a water pressure <6 bar and a flow speed <15 l/min. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 100 2 Connect the hose with non-return valve to the fill and drain kit. Follow the steps described in the previous chapter. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 101: To Insulate The Water Piping

    The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator which can be reached via https://professional.standbyme.daikin.eu. Please contact your dealer if you have no access to Heating Solutions Navigator. This recommendation ensures good operation of the unit, however, local regulations may differ and shall be followed.
  • Page 102: Electrical Installation

    DANGER: RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables. INFORMATION Also read the precautions and requirements in the "2  General safety precautions" [  10]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 103: Guidelines When Connecting The Electrical Wiring

    Stranded conductor wire b Round crimp-style terminal ▪ Use the following methods for installing wires: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 104: About Electrical Compliance

    Equipment complying with EN/IEC  61000‑3‑12 (European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A per phase.). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 105: About Preferential Kwh Rate Power Supply

    9.1.5 Overview of electrical connections except external actuators NOTICE Unlike to other indoor unit model types, Daikin Altherma 3 * ECH₂O always needs a dedicated power supply for the indoor unit. It is NOT possible to use the interconnection cable as power supply for the indoor unit.
  • Page 106: Connections To The Outdoor Unit

    Drain tube heater cable Connection for power saving function (only for V3 models) Air thermistor cable "9.2.2 To reposition the air thermistor on the outdoor unit" [  113]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 107: To Connect The Electrical Wiring To The Outdoor Unit

    ▪ Connect the wires to the terminal block. ▪ Fix the cable with a cable tie. Wires: 1N+GND Maximum running current: Refer to name plate on unit. — EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 108 ▪ Connect the wires to the terminal block (make sure the numbers match with the numbers on the indoor unit) and the earth screw. ▪ Fix the cable with a cable tie. Wires: (3+GND)×1.5 mm² — EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 109 ▪ Fix the cable with cable ties. Wires: (2+GND)×0.75 mm². Wiring must be double insulated. Maximum power allowed for drain tube heater = 115 W (0.5 A) — EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 110 ▪ Connect the wires to the terminal block. ▪ Fix the cable with a cable tie. Wires: 3N+GND Maximum running current: Refer to name plate on unit. — EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 111 ▪ Connect the wires to the terminal block (make sure the numbers match with the numbers on the indoor unit) and the earth screw. ▪ Fix the cable with a cable tie. Wires: (3+GND)×1.5 mm² — EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 112 ▪ Fix the cable with cable ties. Wires: (2+GND)×0.75 mm². Wiring must be double insulated. Maximum power allowed for drain tube heater = 115 W (0.5 A) — EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 113: To Reposition The Air Thermistor On The Outdoor Unit

    9.2.2 To reposition the air thermistor on the outdoor unit This procedure is only necessary in areas with low ambient temperatures. Required accessory (delivered with the unit): Thermistor fixture. Click EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 114: Connections To The Indoor Unit

    Maximum running current: 100 mA For the main zone: ▪ [2.9] Control ▪ [2.A] Thermostat type For the additional zone: ▪ [3.A] Thermostat type ▪ [3.9] (read-only) Control EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 115 ▪ Installation manual of the remote indoor sensor ▪ Addendum book for optional equipment Wires: 2×0.75 mm² [9.B.1]=2 (External sensor = Room) [1.7] Room sensor offset EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 116: To Connect The Electrical Wiring To The Indoor Unit

    To have easier access to the switch box itself and the routing of cables the switch box can be lowered (see "7.2.5 To open the indoor unit" [  72]). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 117 All cables which will be connected to the switch box of the ECH O must be fixed by strain relief. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 118: To Connect The Main Power Supply

    2 Connect the main power supply. In case of normal kWh rate power supply Interconnection cable Wires: (3+GND)×1.5 mm² Power supply indoor Wires: 1N+GND unit Maximum running current: 6.3 A EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 119 Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. [9.8] Benefit kWh power supply EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 120: To Connect The Backup Heater Power Supply

    [9.3] Backup heater WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 121 Z less than or equal to Z Connect the backup heater power supply as follows: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 122 1N~, 50 Hz 230 V AC Model (power supply) Connections to backup heater power supply *3V (3V: 1N~ 230 V) SWB2 Q1DI 1N~, 50 Hz 230 V AC EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 123: To Connect The Backup Heater To The Main Unit

    1 Open the following (see "7.2.5 To open the indoor unit" [  72]): 1 User interface panel 2 Switch box 3 Switch box cover 4 Top cover EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 124: To Connect The Shut-Off Valve

    2 Connect the valve control cable to the appropriate terminals as shown in the illustration below. NOTICE Wiring is different for a NC (normally closed) valve and a NO (normally open) valve. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 125: To Connect The Electricity Meters

    2 Switch box 3 Switch box cover 4 Top cover 2 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 126: To Connect The Domestic Hot Water Pump

    3 Switch box cover 4 Top cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 127: To Connect The Alarm Output

    2 Switch box 3 Switch box cover 4 Top cover 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 128: To Connect The Space Cooling/Heating On/Off Output

    3 Switch box cover 4 Top cover 2 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 129: To Connect The Changeover To External Heat Source

    3 Switch box cover 4 Top cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 130: To Connect The Power Consumption Digital Inputs

    "7.2.5 To open the indoor unit" [  72]): 1 User interface panel 2 Switch box 3 Switch box cover 4 Top cover 2 Install the switch box metal insert. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 131 4 Fix the cable with cable ties to the cable tie mountings. General information, "9.3.1 To connect the electrical wiring to the indoor unit" [  116]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 132: To Connect The Safety Thermostat (Normally Closed Contact)

    X 5M 3 Fix the cable with cable ties to the cable tie mountings. General information, "9.3.1 To connect the electrical wiring to the indoor unit" [  116]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 133: To Connect A Smart Grid

    ([9.A.2] Electricity meter 2 = None) In case of low voltage Smart Grid contacts Wires (Smart Grid pulse meter): 0.5 mm² Wires (low voltage Smart Grid contacts): 0.5 mm² EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 134 2 Fix the cables with cable ties to the cable tie mountings. In case of high voltage Smart Grid contacts Wires (Smart Grid pulse meter): 0.5 mm² Wires (high voltage Smart Grid contacts): 1 mm² EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 135 1 Install the switch box metal insert. 2 Loosen the cables connected to the terminal of the Smart Grid relay kit (EKRELSG) and remove the terminal. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 136 Electrical installation 3 Install the components of the Smart Grid relay kit as follows: 2× 2× EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 137 X15M.6 4 Connect the low voltage wiring as follows: 9 10 X 5M.10 X 5M.9 X 5M 5 Connect the high voltage wiring as follows: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 138: To Connect The Wlan Cartridge (Delivered As Accessory)

    9.3.14 To connect the WLAN cartridge (delivered as accessory) [D] Wireless gateway 1 Insert the WLAN cartridge into the cartridge slot on the user interface of the indoor unit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 139: To Connect The Solar Input

    9.3.16 To connect the DHW output Wires: 2×0.75 mm² Maximum running current: 0.3 A, 230 V AC — 1 Open the following (see "7.2.5 To open the indoor unit" [  72]): EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 140 0,3 A - 230 V AC 3 Fix the cable with cable ties to the cable tie mountings. General information, "9.3.1 To connect the electrical wiring to the indoor unit" [  116]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 141: Configuration

    First time – Configuration wizard. When you turn ON the user interface for the first time (via the unit), the configuration wizard starts to help you configure the system. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 142: To Access The Most Used Commands

    Confirm the pin code and proceed. Installer pin code The Installer pin code is 5678. Additional menu items and installer settings are now available. Installer 5678 EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 143 4 Turn the left dial to select the second part of the setting 01 15 5 Turn the right dial to modify the value from 15 to 20. 01 20 EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 144: To Connect The Pc Cable To The Switch Box

    You can find a short overview of the settings in the configuration here. All the settings can also be adjusted in the settings menu (use the breadcrumbs). For the setting… Refer to… Language [7.1] Time/date [7.2] EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 145 Setpoint mode [2.4] Heating WD curve [2.5] (if applicable) Cooling WD curve [2.6] (if applicable) Schedule [2.1] WD curve type [2.E] Additional zone (only if [4.4]=1) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 146: Possible Screens

    Main menu screen c Lower level screens: c1: Setpoint screen c2: Detailed screen with values c3: Screen with weather-dependent curve c4: Screen with schedule EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 147: Home Screen

    Smart energy is currently being used for domestic hot water. Space operation mode Cooling Heating Outdoor / quiet mode Measured outdoor temperature Quiet mode active Outdoor unit EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 148 Installed heat emitter type: Underfloor heating Fancoil unit Radiator Leaving water temperature setpoint EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 149: Main Menu Screen

    Shows the applicable symbol of your unit. Space heating/ cooling Put the unit in heating mode or cooling mode. You cannot change the mode on heating only models. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 150: Menu Screen

    The setpoint screen is displayed for screens describing system components that need a setpoint value. Examples [1] Room temperature screen [2] Main zone screen °C °C – – Room Main zone EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 151: Detailed Screen With Values

    Selected setting and value Possible actions on this screen Go through the list of settings. Change the value. Go to the next setting. Confirm changes and proceed. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 152: Schedule Screen: Example

    To clear the content of the week schedule 1 Select the name of the current schedule. User defined 1 2 Select Delete. Delete Rename Select 3 Select OK to confirm. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 153 In this example, Monday is the first day you programmed. Thus, the last programmed action is valid up to the first action of next Monday. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 154 5 Repeat this action for all other weekdays. — User defined 1 To program the schedule for Saturday and copy it to Sunday 1 Select Saturday. 2 Select Edit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 155 The schedule name can contain up to 15 characters. 5 Confirm the new name. INFORMATION Not all schedules can be renamed. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 156: Weather-Dependent Curve

    See "10.4.4 Using weather-dependent curves" [  159]. 10.4.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 157: Slope-Offset Curve

    Examples Weather-dependent curve when slope is selected: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 158 The icon corresponds to the heat emitter for that zone: ▪ : Underfloor heating ▪ : Fan coil unit ▪ : Radiator ▪ : Storage tank EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 159: Using Weather-Dependent Curves

    Go to … Main zone – Heating [2.5] Main zone > Heating WD curve Main zone – Cooling [2.6] Main zone > Cooling WD curve EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 160 ↑ Cold Cold ↑ ↑ ↑ ↑ Cold ↓ ↑ ↓ ↑ — ↓ — ↓ Cold ↑ ↓ ↑ ↓ ↓ ↓ ↓ ↓ EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 161: Settings Menu

    No: Room temperature is directly controlled by the user. ▪ Yes: Room temperature is controlled by a schedule and can be modified by the user. Heating schedule Applicable for all models. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 162 Antifrost function via the backup heater. If the backup heater is not allowed for room frost protection during a U4 error, the room Antifrost setting MUST be disabled. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 163 Room frost protection is guaranteed by the normal logic. ▪ The external room thermostat is "Thermo ON" In case of 2 leaving water temperature zones: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 164 NOTICE When adjusting the room temperature ranges, all desired room temperatures are also adjusted to guarantee they are between the limits. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 165: Main Zone

    [9-0A] Heating comfort setpoint ▪ [3-07]~[3-06]°C [1.9.2] [9-0B] Cooling comfort setpoint ▪ [3-09]~[3-08]°C 10.5.3 Main zone Overview The following items are listed in the submenu: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 166 Define a heating temperature schedule for the main zone via [2.2] Heating schedule. "10.3.7 Schedule screen: Example" [  152]. Cooling schedule Define a cooling temperature schedule for the main zone via [2.3] Cooling schedule. "10.3.7 Schedule screen: Example" [  152]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 167 10°C. Heating WD curve Set weather-dependent heating for the main zone (if [2.4]=1 or 2): EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 168 Note: This value should be lower than [1‑02] as for high outdoor temperatures less warm water is required. Cooling WD curve Set weather-dependent cooling for the main zone (if [2.4]=2): EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 169 It is important to set Emitter type correctly and in accordance with your system layout. The target delta T for the main zone depends on it. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 170 Example underfloor heating: 40–5/2=37.5°C To compensate, you can: ▪ Increase the weather-dependent curve desired temperatures [2.5]. ▪ Enable leaving water temperature modulation and increase the maximum modulation [2.C]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 171 Heating maximum: ▪ [2‑0C]=2 (emitter type main zone = radiator) 37°C~70°C ▪ Else: 37°C~55°C [2.8.3] [9-03] Cooling minimum: ▪ 5°C~18°C [2.8.4] [9-02] Cooling maximum: ▪ 18°C~22°C EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 172 Leaving water temperature: Delta T In heating for the main zone, the target delta T (temperature difference) depends on the selected emitter type for the main zone. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 173 Additionally, also the desired leaving water temperature must be configured: if Modulation is enabled, the unit automatically calculates the desired leaving water temperature. These calculations are based on: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 174 1 leaving water temperature zone, connect the shut-off valve to the heating/cooling output. The shut off valve for the main leaving water temperature zone can close under these circumstances: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 175: Additional Zone

    ▪ 1 Yes: closes when the space operation mode is cooling. 10.5.4 Additional zone Overview The following items are listed in the submenu: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 176  152]. Setpoint mode The setpoint mode of the additional zone can be independently set from the setpoint mode of the main zone. "Setpoint mode" [  167]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 177 Note: This value should be lower than [0‑01] as for high outdoor temperatures less warm water is required. Cooling WD curve Set weather-dependent cooling for the additional zone (if [3.4]=2): EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 178 [9‑05]~[9‑06] [1‑0C] 0: Underfloor Maximum 55°C Variable (see [3.B.1]) heating 1: Fancoil unit Maximum 55°C Variable (see [3.B.1]) 2: Radiator Maximum 70°C Fixed 10°C EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 179 (X12M/19) ▪ 2: 2 contacts. Connected to 2 digital inputs (X12M/20 and X12M/19) Leaving water temperature: Delta T For more information, see "10.5.3 Main zone" [  165]. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 180: Space Heating/Cooling

    If your unit is a heating/cooling model, it can both heat up and cool down a space. You have to tell the system which operation mode to use. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 181 2 Select a month. 3 For each month, select an option: ▪ Reversible: Not restricted ▪ Heating only: Restricted ▪ Cooling only: Restricted 4 Confirm the changes. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 182 Example: A unit is configured as following: ▪ Desired room temperature in heating mode: 22°C ▪ Desired room temperature in cooling mode: 24°C ▪ Hysteresis value: 1°C EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 183 INFORMATION Mixing station. If your system layout contains 2 LWT zones, you need to install a mixing station in front of the main LWT zone. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 184 Make sure you set the emitter types for the main zone [2.7] and for the additional zone [3.7] correctly in accordance with the connected emitter. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 185 Sample is ONLY available in leaving water temperature control. a Space heating/cooling control b Off c On d LWT temperature e Actual f Desired g Pump operation EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 186 Possible values: see below. [4.8.2] [9-0D] Restriction: Only displayed when the bizone kit (EKMIKPOA or EKMIKPHA) is installed. Pump limitation Additional zone Possible values: see below. Possible values: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 187 The maximum values depend on the unit type: [9-0D]=0 [9-0D]=1/5 a (kPa) a (kPa) b (l/min) b (l/min) [9-0D]=2/6 [9-0D]=3/7 a (kPa) a (kPa) b (l/min) b (l/min) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 188 0: No ▪ 1: increase 2°C, span 4°C ▪ 2: increase 4°C, span 4°C ▪ 3: increase 2°C, span 8°C ▪ 4: increase 4°C, span 8°C EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 189: Tank

    If powerful operation is active, will be shown on the home screen. To activate powerful operation EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 190 The disinfection function settings MUST be configured by the installer according to the applicable legislation. Code Description [5.7.1] [2‑01] Activation: ▪ 0: No ▪ 1: Yes EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 191 Disinfection mode. Even if you turn OFF tank heating operation ([C.3]: Operation > Tank), disinfection mode will remain active. However, if you turn it OFF while disinfection is running, an AH error occurs. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 192 Code Description [5.9] [6-00] Heat pump ON hysteresis ▪ 2°C~40°C Setpoint mode Code Description [5.B] Setpoint mode: ▪ Fixed ▪ Weather dependent EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 193 Maximum heat pump temperature at sensor in storage tank HP MAX Heat pump OFF temperature (T −[6-01]) HP OFF HP MAX Heat pump ON temperature (T −[6-00]) HP ON HP OFF EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 194: User Settings

    Tank [7.1] Language User settings [7.2] Time/date Information Installer settings [7.3] Holiday [7.4] Quiet [7.5] Electricity price [7.6] Gas price Language Code Description [7.1] Language EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 195 Confirm the changes. 3 Set the last day of your holiday. — ▪ Go to [7.3.3]: Till. ▪ Select a date. ▪ Confirm the changes. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 196 Then you can do the following: 1 Go to [7.4.1]: User settings > Quiet > Activation. 2 Select Most quiet. Advantage: The outdoor unit runs in its most quiet level. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 197 2 Program the selection using the scheduling screen. You can set — the High, Medium and Low electricity prices according to your electricity supplier. 3 Confirm the changes. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 198 Gas price=8.58 Calculation of the electricity price Electricity price=Actual electricity price+Incentive/kWh Electricity price=12.49+5 Electricity price=17.49 Price Value in breadcrumb Gas: 4.08 /kWh [7.6]=8.6 Electricity: 12.49 /kWh [7.5.1]=17 EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 199: Information

    INFORMATION This does not reset the configuration settings and field settings of the indoor unit. Code Description [8.A] Reset the MMI EEPROM to factory default EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 200 Water volume flow rate [l/min] Possible read-out information In menu… You can read out… [8.1] Energy data Produced energy, consumed electricity, and consumed gas, energy flow diagram EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 201: Installer Settings

    [8.B] Piping diagram Real-time sensor and actuator information of the main system components 10.5.9 Installer settings Overview The following items are listed in the submenu: EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 202 This setting is read only. Code Description [9.2.1] [E‑05] ▪ Integrated [E‑06] The backup heater will also be used for domestic hot water heating. [E‑07] EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 203 When measuring the resistance value of each heater, you can set the exact heater capacity and this will lead to more accurate energy data. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 204 If the storage temperature setpoint is higher than 50°C and no auxiliary boiler is installed, Daikin recommends NOT to disable the backup heater second step because it will have a big impact on the required time for the unit to heat up the storage tank.
  • Page 205 The backup heater will ONLY assist if you increase the equilibrium temperature [5‑01] to the required ambient temperature you need to reach the higher setpoint. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 206 [4-06] ▪ 0: Manual ▪ 1: Automatic ▪ 2: auto SH reduced/DHW on ▪ 3: auto SH reduced/DHW off ▪ 4: auto SH normal/DHW off EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 207 If NOT set correctly, the liquid in the piping can freeze. Code Description [E-0D] Glycol Filled system: Is the system filled with glycol? ▪ 0: No ▪ 1: Yes EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 208 1 Heat pump domestic water heating mode (1=active, 0=not active) 2 Hot water request for heat pump (1=request, 0=no request) t Time [8-04]: Additional timer at [4-02]/[F-01] EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 209 Range: 0~95 minutes Water pipe freeze prevention Only relevant for installations with water piping outdoors. This function tries to protect outdoor water piping from freezing. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 210 In case of room buffering, the room will heat up or cool down to the comfort setpoint. In case of tank buffering, the tank will heat up to the maximum tank temperature. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 211 Restriction: Only applicable if [9.8.4] is NOT set to Smart grid. Allow pump: ▪ 0 No: Pump is forced off ▪ 1 Yes: No limitation EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 212 See also below table (Smart Grid operation modes). [9.8.6] Restriction: Only applicable if [9.8.4]=Smart grid. To set if electrical heaters are allowed. Allow electrical heaters: ▪ ▪ EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 213 2 Inputs: Enabled: You can set up to four different power limitation values (in A or kW) to which the system power consumption will be limited when the corresponding digital input asks. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 214 Limits when [9.9.1]=Inputs and [9.9.2]=kW: Code Description [9.9.9] [5-09] Limit 1: 0 kW~20 kW [9.9.A] [5-0A] Limit 2: 0 kW~20 kW [9.9.B] [5-0B] Limit 3: 0 kW~20 kW [9.9.C] [5-0C] Limit 4: 0 kW~20 kW EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 215 (BBR16 activation and BBR16 power limit). After 2 weeks, the unit freezes these settings. Note: This is different from the permanent power limitation, which is always changeable. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 216 ▪ 0 None: NOT installed ▪ 1 1/10kWh: Installed ▪ 2 1/kWh: Installed ▪ 3 10/kWh: Installed ▪ 4 100/kWh: Installed ▪ 5 1000/kWh: Installed EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 217 The outdoor temperature is averaged over the selected time period. Code Description [9.B.3] [1-0A] Averaging time: ▪ 0: No averaging ▪ 1: 12 hours ▪ 2: 24 hours ▪ 3: 48 hours ▪ 4: 72 hours EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 218 (based on energy prices or primary energy efficiency) the auxiliary boiler provides heat for domestic hot water, while the heat pump continues to provide heat for the space heating circuit. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 219 ▪ Boiler efficiency: 0.9 Then: COP=(20/6)×0.9=3 Make sure to use the same units of measurement for the electricity price and gas price (example: both c€/kWh). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 220 Lower values of the PE factor result in increased use of the heat pump. Higher values of the PE factor result in increased use of the auxiliary boiler. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 221 Code Description [9.E] [3-00] Auto restart: ▪ 0: Manual ▪ 1: Automatic EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 222 1: Yes Forced defrost Forced defrost Manually start a defrost operation. Code Description [9.H] Do you want to start a defrost operation? ▪ Back ▪ EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 223 This energy can either be provided by a solar system or an auxiliary boiler connected to the storage tank. The latter is desirable, if the auxiliary heater EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 224 The tank free energy hysteresis defines the storage tank limit temperature, above which heat pump and boiler is stopped in case solar energy is provided and solar priority is active ([C‑00]=0). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 225 1 No: The auxiliary boiler is too small to cover the building demand and is used solely as backup heat source. Therefore, the heat pump is the only available primary heat source. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 226 ▪ 1 No: Heat pump and boiler can operate also while solar energy is provided. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 227 Additional zone pump fixed PWM The speed of the additional zone pump can be fixed with this setting. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 228: Commissioning

    About commissioning See: "11 Commissioning" [  233] 10.5.11 User profile [B] User profile: See "To change the user permission level" [  142]. Installer settings Commissioning User profile Operation Malfunctioning EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 229: Operation

    See: http://www.onlinecontroller.daikineurope.com/ Configuration To configure the Daikin Residential Controller app, follow the in-app instructions. While doing this, the following actions and information are needed on the user interface: Mode: Turn AP mode ON (= WLAN adapter active as access point) or OFF.
  • Page 230 ▪ INFORMATION You can only use this function if it is supported by the software version of the WLAN, and the software version of the Daikin Residential Controller app. Remove from cloud: Remove the WLAN cartridge from the cloud. Code Description [D.4]...
  • Page 231: Menu Structure: Overview User Settings

    (**) Only accessible by installer (***) Only applicable when WLAN is installed INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 232: Menu Structure: Overview Installer Settings

    Mixing valve turning time (*) Only applicable in Swedish language. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 233: Commissioning

    11 Commissioning NOTICE General commissioning checklist. Next to the commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Business Portal (authentication required). The general commissioning checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during the commissioning and hand-over to the user.
  • Page 234: Precautions When Commissioning

    There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units. Backup heater circuit breaker F1B (field supply) is turned ON. The correct pipe size is installed and the pipes are properly insulated. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 235: Checklist During Commissioning

    — reach the minimum required flow rate + 2 l/min. During pump test run, the unit can operate below the minimum required flow rate. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 236: Air Purge Function

    Finally open the two manual air purging valves and check if the circuit is sufficiently filled with water. The air purge function automatically stops after 30 minutes. INFORMATION For best results, air purge each loop separately. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 237 Scroll to Pump speed and set it to Low/High. 7 To stop the air purge manually: — 1 Open the menu and go to Stop air purge. 2 Select OK to confirm. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 238: Operation Test Run

    2 Select OK to confirm. INFORMATION If the outdoor temperature is outside the range of operation, the unit may NOT operate or may NOT deliver the required capacity. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 239: Actuator Test Run

    ▪ Shut off valve test ▪ DHW signal test ▪ Bivalent signal test ▪ Alarm output test EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 240: Underfloor Heating Screed Dryout

    24h (1) 36h (2) 35°C (2) 25°C (1) T Desired leaving water temperature (15~55°C) t Duration (1~72 h) (1) Action step 1 (2) Action step 2 EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 241 "To program an underfloor heating screed dryout schedule" [  240]. Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off Space heating/cooling and Tank operation. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 242 1 Go to [A.4.3]: Commissioning > UFH screed dryout > Status 2 You can read out the value here: Stopped at + the step — where the underfloor screed dryout was stopped. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 243 If the UFH screed dryout program was stopped due to a power failure and the power resumes, the program will automatically restart the last implemented step. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 244: Hand-Over To The User

    Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 245: Maintenance And Service

    Before performing any maintenance or service work, touch a metal part of the unit in order to eliminate static electricity and to protect the PCB. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 246: Yearly Maintenance

    Storage tank water level 13.3.4 Yearly maintenance indoor unit: instructions Water pressure – Space heating/cooling circuit Keep water pressure above 1 bar. If it is lower, add water. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 247 2 Switch box 2 Check if the red level indicator is visible. If NOT, add water to the storage tank (see "8.2.8 To fill the storage tank" [  99]). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 248 Maintenance and service EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 249: Troubleshooting

    If you are unable to find the cause of the problem, call your dealer. DANGER: RISK OF ELECTROCUTION EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 250: Solving Problems Based On Symptoms

    Make sure that the water volume in the too low installation is above the minimum required value (see "8.1.2 To check the water volume and flow rate" [  88]). EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 251: Symptom: Hot Water Does Not Reach The Desired Temperature

    14.3.4 Symptom: The system is making gurgling noises after commissioning Possible cause Corrective action There is air in the system. Purge air from the system. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 252 If yes, make sure that the room where you want to purge air is sufficiently ventilated. Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 253: Symptom: The Pump Is Blocked

    ▪ The valve (if equipped) of the water circuit towards the expansion vessel is open. ▪ The pre-pressure setting of the expansion vessel is correct. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 254: Symptom: The Pressure Relief Valve Opens

    The water pressure Whether there is air in the system The air purge operation EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 255: Symptom: Tank Disinfection Function Is Not Completed Correctly (Ah-Error)

    (disinfection function). The disinfection operation was stopped Do NOT stop tank operation during manually: [C.3] Operation > Tank was disinfection. turned off during disinfection. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 256: Solving Problems Based On Error Codes

    Water flow problem. Pump deblocking active 7H-08 Pump abnormality during operation (pump feedback) 80-01 Returning water temperature sensor problem 81-00 Leaving water temperature sensor problem 81-01 Mixed water thermistor abnormality. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 257 Heat exchanger thermistor abnormality CJ-02 Room temperature sensor problem E1-00 OU: PCB defect E2-00 Leakage current detection error E3-00 OU: Actuation of high pressure switch (HPS) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 258 J6-07 OU: Malfunction of heat exchanger thermistor J6-32 Leaving water temperature thermistor Abnormality (outdoor unit) J6-33 Sensor communication error J8-00 Malfunction of refrigerant liquid thermistor EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 259 U8-09 MMI software version {version_MMI_software} / Indoor unit [version_IU_modelname] compatibility error U8-11 Connection with the Wireless gateway lost UA-00 Indoor unit, outdoor unit matching problem EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 260 If the software is not successfully updated then you must make sure that your USB device has the FAT32 format. INFORMATION The user interface will display how to reset an error code. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 261: Disposal

    See: ▪ "7.3.6 To install the discharge grille" [  79] ▪ "7.3.7 To remove the discharge grille, and put the grille in safety position" [  80] EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 262: To Manually Open The Electronic Expansion Valves

    3 Turn the EEV magnet anticlockwise to the fully open position of the valve. If you are not sure about what the open position is, turn the valve in its middle position so that refrigerant can pass. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 263: Recovery Mode - In Case Of 3N~ Models (7-Segments Display)

    Display the current value. Press BS3 once. Change the value to 2. Press BS2 once. Enter the value in the system. Press BS3 once. Confirm. Press BS3 once. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 264 Result: The recovery mode is deactivated. The unit returns the electronic expansion valves to their initial state. INFORMATION Power OFF. When power is turned OFF and turned ON again, the recovery mode is deactivated automatically. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 265: Recovery Mode - In Case Of 1N~ Models (7-Leds Display)

    = OFF, = ON, and = flashing. Result: The recovery mode is activated. The unit opens the electronic expansion valves. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 266: To Drain The Storage Tank

    2 Unplug the spillover connector. a Spillover connector b Screw plug 3 Connect the loose end of the spillover drain hose to an appropriate drain. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 267 Fill and drain kit b Screw plug 4 Connect the loose end of the drain hose to an appropriate drain. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 268: To Drain The Storage Tank With A Connected Pressureless Solar System

    2 Place an appropriate tray under the drain connection to collect water spillage. 3 Remove the clip and sealing plug. 4 Insert the fill and drain kit and secure with the clip. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 269 Sealing plug c Fill and drain kit 5 Open the valve of the fill and drain kit. 6 Switch the drain connection valve to standard position. EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 270: Technical Data

    Technical data 16 Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). In this chapter 16.1...
  • Page 271: Service Space: Outdoor Unit

    ≥300 ≥100 ≥500 (mm) 3D124412 English Translation General General No top-side obstacle No top-side obstacle Top-side obstacle Top-side obstacle Wall height unrestricted Wall height unrestricted EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 272: Piping Diagram: Outdoor Unit

    Y3E Electronic expansion valve (injection) Y1S Solenoid valve (4-way valve) Y2S Solenoid valve (low pressure bypass) Y3S Solenoid valve (hot gas bypass) Y4S Solenoid valve (liquid injection) Q1E Overload EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 273: Piping Diagram: Indoor Unit

    R2T Thermistor (backup heater – water OUT) R5T, R8T Thermistor (tank) R7T Thermistor (tank - water OUT) S1L Flow switch Screw connection Flare connection Quick coupling Brazed connection EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 274: Wiring Diagram: Outdoor Unit

    See note *** See note *** Only for *W1 models. Notes: Symbols: Live Neutral Protective earth Noiseless earth Field wiring Option Terminal strip Terminal Connector Connection EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 275 K1R (A1P) Magnetic relay (Y1S) K1R (A4P) Magnetic relay (E1HHEX) K2R (A1P) Magnetic relay (Y2S) K2R (A4P) Magnetic relay (E1H) K3R (A1P) Magnetic relay (Y3S) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 276 Solenoid valve (4‑way valve) Solenoid valve (low pressure bypass) Solenoid valve (hot gas bypass) Solenoid valve (liquid injection) Z1C~Z11C Noise filter (ferrite core) Z1F~Z5F (A1P, A2P) Noise filter EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 277 Thermistor (compressor discharge) Thermistor (compressor suction) Thermistor (air heat exchanger, liquid pipe) Thermistor (air heat exchanger, middle) Thermistor (refrigerant liquid) Thermistor (injection) Thermistor (entering water) EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 278 Solenoid valve (4‑way valve) Solenoid valve (low pressure bypass) Solenoid valve (hot gas bypass) Solenoid valve (liquid injection) Z1C~Z11C Noise filter (ferrite core) Z1F~Z6F (A1P, A2P) Noise filter EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 279: Wiring Diagram: Indoor Unit

     Safety thermostat  Safety thermostat Main LWT Main leaving water temperature  On/OFF thermostat (wired)  On/OFF thermostat (wired)  On/OFF thermostat (wireless)  On/OFF thermostat (wireless)  Ext. thermistor  External thermistor EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 280 # Domestic hot water pump # 2-way valve for cooling mode PC (A15P) * Power circuit Thermal protector backup heater # Safety thermostat Q*DI # Earth leakage circuit breaker EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 281 Alarm output Alarm output BUH option Backup heater option BUH option only for * Backup heater option only for * Bizone mixing kit Bizone mixing kit EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 282 Space C/H On/OFF output Space cooling/heating On/OFF output SWB1 Switch box (4) Option PCBs (4) Option PCBs Only for demand PCB option Only for demand PCB option EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 283 Only for wireless On/OFF thermostat Only for wireless On/OFF thermostat (6) Backup heater power supply (6) Backup heater power supply Only for *** Only for *** SWB2 Switch box EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 284 Power limitation demand input 4 Only for remote user interface A8P: X801M: 4-5 2 core signal 2×0.75 X 5M: 11-12 A14P: P1-P2 user interface communication 4D132247 EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 285: Esp Curve: Indoor Unit

    Operating pressure of storage water pH k Domestic hot water volume (heat exchanger) l Max. operating pressure PMS (drinking water installation) m Nominal voltage U EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 286 Technical data n Rated current of fuse o Protection type p Backup heater (optional) q Part number r Revision EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF Installer reference guide Daikin Altherma 3 H MT ECH₂O 4P663478-1 – 2021.07...
  • Page 287: Glossary

    Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
  • Page 288: Field Settings Table

    1/13 0791 Field settings table [8.7.5] = ..Applicable indoor units ETSH12P30EF ETSH12P50EF ETSHB12P30EF ETSHB12P50EF ETSX12P30EF ETSX12P50EF ETSXB12P30EF ETSXB12P50EF Notes (*1) 300 Tank (*2) 500 Tank (*3) *X* (*4) *H* (*5) *B* (*6) EKECBUA3V (*7) EKECBUA6V (*8) EKECBUA9W (*9) BUH less 4P670987-1 - 2021.09...
  • Page 289 2/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value Room └─ Antifrost 1.4.1 [2-06] Activation 0: Disabled 1: Enabled 1.4.2 [2-05] Room setpoint 4~16°C, step: 1°C 8°C └─...
  • Page 290 3/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value └─ Shut off valve 2.D.1 [F-0B] During thermo 0: No 1: Yes 2.D.2 [F-0C] During cooling 0: No 1: Yes Main zone WD curve type...
  • Page 291 4/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [F-00] Pump outside range 0: Restricted 1: Allowed [D-03] Increase around 0°C 0: No 1: increase 2°C, span 4°C 2: increase 4°C, span 4°C 3: increase 2°C, span 8°C 4: increase 4°C, span 8°C...
  • Page 292 5/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.1.3.8 [C-02] Bivalent 0 none 1 bivalent through header 2 tank DHW bivalent (*5) 3 tank heating + DHW bivalent 9.2.4 [D-07] Solar...
  • Page 293 6/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.1.A [0-04] Leaving water value for high ambient temp. for LWT add zone cooling WD curve. [9-07]~[9-08]°C, step: 1°C [2-0C]=0: 18°C [2-0C]=1:...
  • Page 294 7/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.8.2 [D-00] Allow heater 0: None 1: BSH only 2: BUH only 3: All heaters 9.8.3 [D-05] Allow pump 0: Forced off 1: As normal 9.8.4...
  • Page 295 8/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. [9-05]~min(45,[9-06])°C, step: 1°C [2-0C]=0: 25°C [2-0C]=1:...
  • Page 296 9/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [2-00] When should the disinfection function be executed? 0: Each day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday...
  • Page 297 10/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [5-04] Set point correction for domestic hot water temperature. 0~20°C, step: 1°C 10°C [5-05] What is the requested limit for DI1? 0~50 A, step: 1 A 50 A [5-06]...
  • Page 298 11/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [8-08] What is the desired eco main LWT in cooling? [9-03]~[9-02], step: 1°C 20°C [8-09] What is the desired comfort main LWT in heating? [9-01]~[9-00], step: 1°C 35°C [8-0A]...
  • Page 299 12/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [D-04] Is a demand PCB connected? 0: No 1: Pwr consmp ctrl [D-05] Is the pump allowed to run if prefer. kWh rate PS is cut? 0: Forced off 1: As normal [D-07]...
  • Page 300 13/13 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.P.1 [E-0B] Bizone kit installed 0: Not installed 1: - 2: Bizone kit installed 9.P.2 [E-0C] Bizone system type 0: Without hydraulic separator / no direct pump 1: With hydraulic separator / no direct...
  • Page 304 4P663478-1 2021.07 Verantwortung für Energie und Umwelt...

Table of Contents