Daikin EPRA10EAV3 Installer's Reference Manual page 188

Table of Contents

Advertisement

10
|
Configuration
Installer reference guide
188
Value
0
No limitation
1~4
General limitation. There is limitation in all conditions. The
required delta T control and comfort are NOT guaranteed.
1: 90% pump speed
2: 80% pump speed
3: 70% pump speed
4: 60% pump speed
5~8
Limitation when no actuators. When there is no heating output,
the pump speed limitation is applicable. When there is heating
output, the pump speed is only determined by delta T in
relation to the required capacity. With this limitation range,
delta T is possible and the comfort is guaranteed.
During sampling operation the pump runs for a short time to
measure the water temperatures, which indicate if operation is
required or not.
5: 90% pump speed during sampling
6: 80% pump speed during sampling
7: 70% pump speed during sampling
8: 60% pump speed during sampling
The maximum values depend on the unit type:
[9-0D]=0
a (kPa)
[9-0D]=2/6
a (kPa)
Description
[9-0D]=1/5
a (kPa)
b (l/min)
[9-0D]=3/7
a (kPa)
b (l/min)
b (l/min)
b (l/min)
EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07