10
|
Configuration
Installer reference guide
192
#
Code
[5.7.2]
[2‑00]
[5.7.3]
[2‑02]
[5.7.4]
[2‑03]
[5.7.5]
[2‑04]
T
DHW
[2-03]
T
H
T
U
00.00
01.00
T
Domestic hot water temperature
DHW
T
User setpoint temperature
U
T
High setpoint temperature [2-03]
H
t Time
WARNING
Be aware that the domestic hot water temperature at the hot water tap will be equal
to the value selected in field setting [2-03] after a disinfection operation.
When the high domestic hot water temperature can be a potential risk for human
injuries, a mixing valve (field supply) shall be installed at the domestic hot water out
connection of the storage tank. This mixing valve shall secure that the hot water
temperature at the hot water tap never rise above a set maximum value. This
maximum allowable hot water temperature shall be selected according to the
applicable legislation.
CAUTION
Make sure that the disinfection function start time [5.7.3] with defined duration
[5.7.5] is NOT interrupted by possible domestic hot water demand.
NOTICE
Disinfection mode. Even if you turn OFF tank heating operation ([C.3]: Operation >
Tank), disinfection mode will remain active. However, if you turn it OFF while
disinfection is running, an AH error occurs.
Operation day:
0: Every day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
Start time
Tank setpoint:
60°C
Duration:
40~60 minutes
[2-04]
22.00
23.00
24.00
t
[2-02]
Description
EPRA08~12EAV3+W1 + ETSH/X(B)12P30+50EF
Daikin Altherma 3 H MT ECH₂O
4P663478-1B – 2022.07