14. Go to Program Parameters and Local Tags. On the bottom of the window, select the tab
Monitor tags. If the connection is successful, the data from the sensor shows.

5.4.2.1 Configure the EtherNet/IP data structure

Use the data structure to group the data types. When the data structure is used in the Ethernet/IP
module, make sure to set the order in the controller based on the variable type: all float values first
and then all of the integer values.
To configure the EtherNet/IP module with a data structure, do the steps that follow:
1. Do steps
1
to
3
on .
2. On the controller, select Main menu > Outputs > EtherNet/IP > Telegram > [device/sensor] >
Tag list. Use the drag and drop function to change the tag position. Push and hold near the blue
dots icon of the tag, then move the tag to the new position. Move the tags so that the float and
integer values are together.
3. Push OK, then Save.
36 English