Figure 7 Wiring example
1 PLC
2 Industrial switch

Section 4 Startup

1. Supply power to the controller and PLC.
2. Set the PLC to on.

Section 5 Operation

5.1 Configure the Ethernet ports

Make sure that the Ethernet port configuration in the controller is set to one of the IEP (industrial
Ethernet ports) options.
1. Push the main menu icon, then select Controller > Connectivity > LAN > Ethernet ports.
2. Select one of the options that follow based on the wiring configuration of the controller.
Option
Description
IEP only The two Ethernet ports are configured for PROFINET or EtherNet/IP. Port 2 in the
module is enabled. Refer to
MIX IEP One Ethernet port is configured for LAN connectivity and the other Ethernet port is
configured for PROFINET or EtherNet/IP. Port 2 in the module is disabled. Refer to
Figure 5
Note: When Mix IEP is selected, LAN port configuration shows in the LAN menu. LAN port
configuration setting is used only for LAN connectivity configuration, not for Industrial Ethernet
port configuration.
8 English
Figure 6
on page 6.
3 SC4500 controller
4 Laptop
on page 7.