Alarm
High Discharge Pressure,
cont'd PSH
6 - 1 0
l Tr o u b l e s h o o t i n g
T I C C o n t r o l A l a r m C o n d i t i o n s
Possible cause
Valves were removed.
Overcharged with refrigerant.
Faulty optional water regulating valve.
Faulty pressure switch.
Solution
See Checking the Refrigerant Charge in
the Maintenance section.
Repair or replace the valve.
See Checking the Pressure Switches, in
the Troubleshooting section.
( c o n t i n u e d )