P L C C o n t r o l A l a r m C o n d i t i o n s
Alarm
Comp Fault alarm
OR
Compressor 2 comp Fault
(dual pump models)
Possible cause
Compressor is wired incorrectly.
Compressor module is faulty.
Loss of 120 VAC to module.
Solution
Shut off chiller supply voltage. Switch
any two leads:
• at compressor if it was replaced.
• at main terminal block if new unit
installation.
Turn chiller on.
See Checking the Compressor module
spec's in the Troubleshooting section.
Check power to T1 and T2 Term on
module. See compressor module.
Tr o u b l e s h o o t i n g l
6 - 2 9