P L C C o n t r o l S e t t i n g A u t o Tu n e M o d e
C o n t i n u e d
The password screen displays.
4
Use the keypad to enter the password. The factory set password is 999.
5
Press the Enter button to enter the password.
6
Press the Scroll arrows to scroll to the Tune screen.
7
Press the Tune arrow.
TUNE
TUNE
When the control begins tuning the screen displays TUNING message. The auto-tun-
ing sequence takes about 15 seconds. The screen displays the 'TUNE Tuning' mes-
sage. When tuning is complete, the screen displays the TUNE message. Press the
Abort arrow to stop the auto-tuning sequence and return to the last good PID values.
8
Press the Escape/Previous Screen button to exit the Maintenance
screens and return to the main screen.
ABORT
press arrow
M a i n t e n a n c e l
5 - 1 3