P L C C o n t r o l S e t t i n g D i s c h a r g e
P r e s s u r e S e t p o i n t
You can select the refrigerant discharge pressure setpoints in PSIG. To set the dis-
charge pressure setpoints from the main screen:
1
Press the Setup arrow.
STATUS SETUP RUN ALM
2
Press the Scroll arrows to scroll through the Setup screens. Stop when you get
to the PID Reset screen.
PID Reset
DPS
3
Press the DPS arrow. The Discharge Pressure Setpoint screen displays.
Press SP
225 PSIG
Press PV
240 PSIG
process variable (PV), both in PSIG are listed. Change the value of the pressure
setpoint by entering the new number with the Select Value buttons.
The discharge pressure can be set between 100 and 350 PSIG.
3
Press the Enter button to accept the new value.
press arrow
FANS
press arrow
The pressure setpoint (SP) and the pressure
O p e r a t i o n l
4 - 2 9