T I C C o n t r o l A l a r m C o n d i t i o n s
Alarm
Flow fault (pump and com-
pressor are off) "FAL"
Possible cause
The optional To Process and/or From
Process valves are closed.
The Process Fluid strainer is clogged.
Water level in reservoir is low.
The evaporator is fouled.
Pump is not running.
Pump is running backwards.
( c o n t i n u e d )
Solution
Open valve(s).
Clean the evaporator strainer.
Fill the reservoir. See Making Process
Plumbing Connections, in the
Installation section.
Clean Evaporator. See Cleaning the
Evaporator or Water-cooled Condenser,
in the Maintenance section.
Check overload module. Replace as
needed. See Replacing Overload
Modules, in the Troubleshooting section.
Switch any two of the three main power
leads to the pump.
Tr o u b l e s h o o t i n g l
6 - 1 3