Plc Control; Initially Warming The Chiller - Conair PCW-1.5 User Manual

Portable chillers
Table of Contents

Advertisement

3 - 1 4
l I n s t a l l a t i o n
P L C C o n t r o l I n i t i a l l y Wa r m i n g t h e
C h i l l e r
WA R N I N G : I n i t i a l s t a r t u p
Do not press any buttons after initially applying power to the chiller. Let the
chiller set, undisturbed, for a minimum of 8 hours before starting the
chiller. This is necessary to allow the crank case heater to warm properly,
and to prevent the refrigerant from pooling in the compressor.
1
Turn on main power source. The control boots up and when finished, the
screen displays "Press enter to continue."
2
Press enter. This screen will appear.
3
Press next. The screen displays information about the chiller, which includes
the model, series, size, and serial number. The menu options are listed on the
bottom of the screen ("Stat Setup Run Alarm"). The "Select Option" key button
located under each of the menu options is used to navigate to the corresponding
menu option. Record the data from this screen in the front of your manual. You
will need this information for any parts or service related question. (See page 4-
17 to understand your model number.)
4
Pump, compressor and alarm indicator lamps will flash three times. The
compressor lamp will flash an additional three minutes.
Conair Chiller
PCW - 30 123456
PCW-15R Size 2
Serial No.: 123456
Stat Setup Run Alarm